M-Max Series Overview
14 M-Max Series Adjustable Frequency Drive MN04020003E—October 2013 www.eaton.com
Block Diagram, Elements of M-Max Frequency Inverters
Item
Number Description
1 Supply L1, L2/N, L3, PE, mains supply voltage U
LN
= U
e
at 50/60 Hz:
MMX11: 100V class, single-phase mains connection (1 AC 120V),
MMX12: 200V class, single-phase mains connection (1 AC 230V/240V),
MMX32: 200V class, three-phase mains connection (3 AC 230V/240V),
MMX34: 400V class, three-phase mains connection (3 AC 400V/480V).
MMX35: 575V class, three-phase input connection (3 AC 575V)
2 Internal RFI filter (MMX…F_), category C2 and C3, in accordance with IEC/EN 61800-3
EMC connection of internal RFI filter with PE.
3 Rectifier bridge, single-phase (MMX1_) or three-phase (MMX3_), converts the AC voltage of the electrical network into DC voltage
4 DC choke, DC link choke (only for MMX32…F_ and MMX34…F_ in frame sizes FS4 and FS5)
5 DC link with charging resistor, capacitor and switching-mode power supply unit
(SMPS = Switching-Mode Power Supply): DC link voltage U
DC
: U
DC
= 1.41 x U
LN
6 Braking transistor: connections DC+/R+ and R- for external braking resistor (only for MMX32 and MMX34 from frame size FS2)
7 Inverter. The IGBT based inverter converts the DC voltage of the DC link (U
DC
) into a three-phase AC voltage (U
2
) with variable amplitude and
frequency (f
2
). Sinusoidal pulse width modulation (PWM) with V/f control can be switched to speed control with slip compensation
8 Motor connection U/T1, V/T2, W/T3 with output voltage U2 (0 to 100 % U
e
) and output frequency f2 (0 to 320 Hz) output current (I
2
):
MMX11: 1.7 – 4.8A,
MMX12: 1.7 – 9.6A,
MMX32: 1.7 – 38A,
MMX34: 1.3 – 38A,
MMX35: 1.7 – 9.0A
100% at an ambient temperature of +50°C with an overload capacity of 150% for 60s every 600s and a starting current of 200% for 2s every 20s
9 Three-phase asynchronous motor, variable speed control of three-phase asynchronous motor for assigned motor shaft power values (P
2
):
MMX11: 0.25 – 1.1 kW (230V, 50 Hz) or 0.33 – 1 hp (230V, 60 Hz),
MMX12: 0.25 – 2.2 kW (230V, 50 Hz) or 0.25 – 3 hp (230V, 60 Hz),
MMX32: 0.25 – 11 kW (230V, 50 Hz) or 0.25 – 15 hp (230V, 60 Hz),
MMX34: 0.37 – 18.5 kW (400V, 50 Hz) or 0.5 – 25 hp (460V, 60 Hz),
MMX35: 1–7.5 hp (575V, 60 Hz)
10 Keypad with control buttons, LCD display, control voltage, control signal terminals, microswitches and interface for the PC interface card (Option)
+
DC+/R+
EMC
L1
L2/N
L3
PE
R-
M
3 ~
U/T1
V/T2
W/T3
PE
1
2
3
4
5
6
7
8
9
10