Effective 10/02
Page 4-10Page 4-10
For more information visit: www.cutler-hammer.eaton.comIL17562BH04
Selected
Value
Line
No.
1
1
1
2
3
Display
Choose:
REM RST
REM TRIP
DIF TRIP
MTR STOP
RST DBL
EMG OVR
ZERO SW
Choose:
REM RST
REM TRIP
DIF TRIP
MTR STOP
RST DBL
EMG OVR
INC SEQ
Choose:
GF A ON
GF T ON
or
GF OFF
Choose:
I2T A ON
I2T T ON
or
I2T OFF
Choose:
JAM A ON
JAM T ON
or
JAM OFF
Help Message
CONFIGURE DISCRETE INPUT 1 - -
REM RST – REMOTE RESET
REM TRIP – REMOTE TRIP
DIF TRIP – DIFFERENTIAL TRIP
MTR STOP – MOTOR STOP DETECTION
RST DBL – RESET DISABLE
EMG OVR – EMERGENCY OVERRIDE
ZERO SW – ZERO SPEED SWITCH
CONFIGURE DISCRETE INPUT 1 –
ZERO SW – ZERO SPEED SWITCH TO
GET ANY OTHER FUNCTION SET ZERO
SPEED SWITCH SETTING TO OFF
CONFIGURE DISCRETE INPUT 2 - -
REM RST – REMOTE RESET
REM TRIP – REMOTE TRIP
DIF TRIP – DIFFERENTIAL TRIP
MTR STOP – MOTOR STOP DETECTION
RST DBL – RESET DISABLE
EMG OVR – EMERGENCY OVERRIDE
INC SEQ – INCOMPLETE SEQUENCE
CONFIGURE DISCRETE INPUT 2 –
INC SEQ – INCOMPLETE
SEQUENCE TO GET ANY OTHER FUNC-
TION SET INCOMPLETE SEQUENCE
TIME SETTING TO OFF
ENABLE GROUND FAULT ALARM OR
TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
ENABLE I2T ALARM OR TRIP TO ACTI-
VATE ALARM RELAY OUTPUT OR
DISABLE
ENABLE JAM ALARM OR TRIP TO
ACTIVATE ALARM RELAY OUTPUT OR
DISABLE
Setting
Range/ Value
Selection
Choose from the
seven selections
for the function of
Discrete Input 1.
If ZERO SW is
selected here,
P5L11 will be
forced to ZSW
ON.
If P5L11 was
already set to ZSW
ON, then this
setting is auto-
matically set to
ZERO SW and no
other selections
are visible.
Choose from the
seven selections
for the function of
Discrete Input 2.
If INC SEQ is
selected here,
P5L8 will be
turned on and set
to 1 second.
If P5L8 was
already set to a
time value (not
OFF), then this
setting is auto-
matically set to
INC SEQ and no
other selections
are visible.
Toggles between
GF A ON, GF T
ON, and GF OFF
Toggles between
I2T A ON, I2T T
ON, and I2T OFF
Toggles between
JAM A ON, JAM T
ON, and JAM OFF
Value
as
shipped
REM
RST
INC SEQ
GF A
ON
I2T A ON
JAM A
ON
Section
Reference
5.6.1
5.7.1
5.8
5.8
5.8
Page 6 SP DI 1 SETTING FOR DISCRETE INPUT NUMBER 1
Page 7 SP DI 2 SETTING FOR DISCRETE INPUT NUMBER 2
Page 8 SP AREL SETTING FOR ALARM RELAY OUTPUT CONFIGURATION