Effective 10/02
Page 4-17
For more information visit: www.cutler-hammer.eaton.com
Page 4-17
IL17562BH04
Selected
Value
3-Phase
Line
No.
7
8
9
10
11
12
13
14
15
16
17
18
1
Display
EMRG EN
or
EMRG DIS
12 HOUR
or
24 HOUR
MONTH XX
DAY XX
YEAR XX
HOUR XX
MIN XX
M D Y
or
D M Y
IQ2 EN
or
IQ2 DIS
RLYF TRP
RLYF ALM
or
RLYF T+A
INCT DIS
or
INCT EN
DISARMED
or
ARMED
3 PHASE
or
1 PHASE
Help Message
EMERGENCY OVERRIDE ENABLE
EMRG EN – ENABLE EMERGENCY
OVERRIDE
EMRG DIS – DISABLE EMERGENCY
OVERRIDE
SET REAL TIME CLOCK DISPLAY
12 HOUR – AM/PM TIME DISPLAYED
13 24 HOUR – 24 HOUR TIME DISPLAYED
SET REAL TIME CLOCK MONTH
SET REAL TIME CLOCK DAY
SET REAL TIME CLOCK YEAR
SET REAL TIME CLOCK HOUR
SET REAL TIME CLOCK MINUTE
SET REAL TIME DATE DISPLAY
MONTH DAY YEAR OR
DAY MONTH YEAR
IMPACC COMMUNICATIONS MODE
IQ2 EN – IQ1000II EMULATION
IQ2 DIS – MP-3000 COMMUNICATION
INTERNAL DIAGNOSTIC FAILURE
ACTIVATES TRIP AND OR ALARM
RELAY
INCOM TRIP DISABLED OR ENABLED
ARM OR DISARM TRIP RELAY
WARNING DISARM WILL NOT ALLOW
TRIP RELAY TO FUNCTION
TRIP WARNING MP-3000 WILL BE
DISARMED UPON EXIT OF PROGRAM
MODE AND WILL NOT PROTECT THE
MOTOR-ENTER ARMED INTO SETTING
TO PROTECT THE MOTOR
SINGLE PHASE TEST MODE OR THREE
PHASE PROTECTION MODE
Setting
Range/ Value
Selection
Toggles between
EMRG EN and
EMRG DIS
Toggles between
12 HOUR and 24
HOUR
Month 1-12 (1
month increments)
Day 1-31 (1 day
increments)
Year 0-99 (1 year
increments)
Hour 0-23 (1 hour
increments)
Minute 0-59 (1
minute increments)
Toggles between
M D Y and D M Y
Toggles between
IQ2 EN and IQ2
DIS
Toggles between
RLYF TRP, RLYF
ALM and RLYF
T+A
Toggles between
INCT DIS and
INCT EN
Toggles between
ARMED and
DISARMED
Toggles between
3-PHASE and 1-
PHASE
Note: 1-PHASE is
for bench testing
ONLY.
Value
as
shipped
EMRG DIS
12 HOUR
—
—
—
—
—
M D Y
IQ2 DIS
RLYF T+A
INCT EN
ARMED
3-PHASE
Section
Reference
5.12.7
5.12.8
5.12.9
5.12.10
5.12.11
5.12.12
5.12.13
5.12.14
5.12.15
5.12.16
5.12.17
5.12.18
5.13.1
Page 13 SP TEST SETTINGS FOR TESTING INPUTS AND OUTPUTS