Effective 10/02
Page 4-16Page 4-16
For more information visit: www.cutler-hammer.eaton.comIL17562BH04
Section
Reference
5.10.2
5.10.2
5.10.2
5.10.2
5.10.2
5.11.1
5.12.1
5.12.2
5.12.3
5.12.4
5.12.5
5.12.6
Selected
Value
Line
No.
19
20
21
22
23
1
1
2
3
4
5
6
Display
DIFT OFF
or
DIFT OFF
INCT ON
or
INCT OFF
TRNT ON
or
TRNT OFF
ZSWT ON
or
ZSWT OFF
TBYP ON
or
TBYP OFF
MAX 100
MAX 125
MAX WRTD
MAX %12T
TP MODE X
AL MODE X
AX1 MOD X
AX2 MOD X
MAN I2T
or
AUTO I2T
RUN PGM
or
STOP PGM
Help Message
ENABLE DIFFERENTIAL TRIP TO
ACTIVATE AUX2 RELAY OUTPUT
OR DISABLE
ENABLE INCOM TRIP TO ACTIVATE
AUX2 RELAY OUTPUT OR DISABLE
ENABLE TRANSITION TRIP TO ACTIVATE
AUX2 RELAY OUTPUT OR DISABLE
ENABLE ZERO SPEED SWITCH TRIP
TO ACTIVATE AUX2 RELAY OUTPUT
OR DISABLE
ENABLE TRIP BYPASS TO ACTIVATE
AUX2 RELAY OUTPUT OR DISABLE
4-20 MA OUTPUT
MAX 100 – 20 MA FOR 100% FLA
MAX 125 – 20 MA FOR 125% FLA
MAX WRTD – 20 MA FOR TRIP LEVEL
MAX %I2T – 20 MA FOR 100% I2T
CONFIGURE TRIP RELAY OUTPUT TO
BE MODE 1 – TRIP RELAY ENERGIZES
ON TRIP EVENT OR MODE 2 – TRIP
RELAY ENERGIZES ON POWER UP
AND DE-ENERGIZES ON TRIP EVENT
CONFIGURE ALARM RELAY OUTPUT TO
BE MODE 1 – ALARM RELAY ENERGIZES
ON ALARM EVENT OR MODE 2 – ALARM
RELAY ENERGIZES ON POWER UP AND
DE-ENERGIZES ON ALARM EVENT
CONFIGURE AUX1 RELAY OUTPUT TO
BE MODE 1 – AUX1 RELAY ENERGIZES
ON AUX1 EVENT OR MODE 2 – AUX1
RELAY ENERGIZES ON POWER UP
AND DE-ENERGIZES ON AUX1 EVENT
CONFIGURE AUX2 RELAY OUTPUT TO
BE MODE 1 – AUX2 RELAY ENERGIZES
ON AUX2 EVENT OR MODE 2 – AUX2
RELAY ENERGIZES ON POWER UP
AND DE-ENERGIZES ON AUX2 EVENT
AUTO OR MANUAL I2T RESET
ENABLES UNIT TO BE PROGRAMMED
WHILE MOTOR IS RUNNING
Setting
Range/ Value
Selection
Toggles between
DIFT ON and
DIFT OFF
Toggles between
INCT ON and
INCT OFF
Toggles between
TRNT ON and
TRNT OFF
Toggles between
ZSWT ON and
ZSWT OFF
Toggles between
TBYP ON and
TBYP OFF
Select one of MAX
100, MAX 125,
MAX WRTD, or
MAX %I2T
Toggles between
TP MODE1 and
TP MODE2
Toggles between
AL MODE1 and
AL MODE2
Toggles between
AX1 MOD1 and
AX1 MOD2
Toggles between
AX2 MOD1 and
AX2 MOD2
Toggles between
MAN I2T and
AUTO I2T
Toggles between
RUN PGM and
STOP PGM
Value
as
shipped
DIFT OFF
INCT OFF
TRNT OFF
ZSWT
OFF
TBYP
OFF
MAX 125
TP MODE2
AL MODE2
AX1
MOD1
AX2
MOD1
MAN I2T
STOP
Page 11 SP A OUT SETTING FOR ANALOG OUTPUT CONFIGURATION
Page 12 SP SYS SETTINGS FOR SYSTEM CONFIGURATION