Effective 10/02
Page 4-24Page 4-24
For more information visit: www.cutler-hammer.eaton.comIL17562BH04
Page
LOG EVNT
Line
TRIP
ALARM
TRIP
Or
ALARM
Description
For a complete list of trips with help
messages see the trip conditions table
12.2, and internal diagnostics failure
messages table 12.4
The date that the event occurred
The time that the event occurred
For a complete list of alarms with help
messages see the alarm conditions
table 12 .2, and internal diagnostics
failure messages table 12.4
The date that the event occurred
The time that the event occurred
This page contains detailed trouble
shooting information for all trip and
alarm events. The events are logged
chronologically. From this display
press line up to get the most recent
event. Push again for the next most
recent event and so on. From this
display press line down to get the
oldest event. Push again for the next
oldest event.
A trip or alarm event was logged. For
a complete list see the trip conditions
table 12.2, and internal diagnostics
failure messages table 12.4
The date that the trip occurred
The time that the trip occurred
The phase current in amps at time of
trip
The ground fault current in amps at
time of trip
The percent of thermal bucket used at
time of trip
The percent sequence current
unbalance at time of trip
RTD temperatures at time of trip
Complete Help Message
(Description of trip event)
DATE OF EVENT
TIME OF EVENT
(Description of alarm event)
DATE OF EVENT
TIME OF EVENT
DETAILED LOG OF THE LAST 20
ABNORMAL EVENTS
(Description of trip or alarm event)
DATE OF EVENT
TIME OF EVENT
PHASE A CURRENT IN AMPS AT TIME
OF EVENT
PHASE B CURRENT IN AMPS AT TIME
OF EVENT
PHASE C CURRENT IN AMPS AT TIME
OF EVENT
GROUND FAULT CURRENT IN AMPS
AT TIME OF EVENT
PERCENT OF I2T TRIP LEVEL AT TIME
OF EVENT
PHASE UNBALANCE AT TIME OF THE
EVENT - IF POSITIVE THE RATIO OF
NEGATIVE TO POSITIVE SEQUENCE
CURRENT – IF NEGATIVE THE INVERSE
WINDING TEMP 1 IN DEGREES (F OR
C) AT TIME OF EVENT”
WINDING TEMP 2 IN DEGREES (F OR
C) AT TIME OF EVENT” WINDING
TEMP 3 IN DEGREES (F OR C) AT
TIME OF EVENT”
WINDING TEMP 4 IN DEGREES (F OR C)
AT TIME OF EVENT”
WINDING TEMP 5 IN DEGREES (F OR
C) AT TIME OF EVENT”
WINDING TEMP 6 IN DEGREES (F OR
C) AT TIME OF EVENT”
MOTOR BEARING TEMP 1 IN
DEGREES (F OR C) AT TIME OF EVENT
Display
MM/DD/YY
HH.MM
MM/DD/YY
HH.MM
MM/DD/YY
HH.MM
IA XXX
IB XXX
IC XXX
IG XXX
%I2T XXX
%UB XXX
WT1 XXX
WT2 XXX
WT3 XXX
WT4 XXX
WT5 XXX
WT6 XXX
MT1 XXX

Table of Contents