www.eaton.com Page 4-7
MP-4000 IB02602002E
Table 4-3. View Setting Mode/Program Worksheet.
SUB-
MENU
LINE # DISPLAY HELP MESSAGE SETTING RANGE/VALUE
(DEFAULT SELECTION AND
VALUE AS SHIPPED IN BOLD)
VALUE SELECTED
VIEW SP VIEW PROGRAM SETTINGS
PAGE 1, SP MOTOR SETTINGS FOR MOTOR CONSTANTS
1 FLA XXXX FULL LOAD AMPS
10-3,000 amps in 1 amp. increments (10)
2 LRC XXXX LOCKED ROTOR CURRENT % OF FLA
300-1,200% in 1% increments (300)
3 LRT XXX MAXIMUM ALLOWABLE STALL TIME IN
SECONDS
1-120 sec. in 1 sec. increments (300)
4 UTC XXX ULTIMATE TRIP CURRENT IN %FLA
85-150% in 1% increments (1)
5 PCT XXXX PHASE CT RATIO NUMERATOR IN
PRIMARY AMP
10-4,000 A in increments of 1 (10)
6 GCT XXXX GROUND CT RATIO NUMERATOR IN
PRIMARY AMP
10-4,000 A in increments of 1 (50)
7 FREQ 50
or FREQ 60
50 - FOR 50 HERTZ LINE FREQUENCY
60 - FOR 60 HERTZ LINE FREQUENCY
Toggles between FREQ 50 and FREQ 60
8 REV or NON
REV
REVERSING OR NON REVERSING
STARTER
Toggles between REV and NON REV
9 STOP X MOTOR STOP CURRENT LEVEL IN
% OF PHASE CT RATIO NUMERATOR
2-20% of phase CT ratio numerator in 1%
increments (5%)
PAGE 2, SP RTD SETTINGS FOR RTD INPUTS
1 RTD IN C
or
RTD in F
DISPLAYED IN DEGREES C OR F
Toggles between RTD IN C and RTD IN F
2 WD T XXX WINDING TEMP TRIP 0-199 C, OFF/32-390 F, OFF in 1 increments
(100)
3 WD A XXX WINDING TEMP ALARM
0-199 C, OFF/32-390 F, OFF in 1 increments
(80)
4 MB T XXX MOTOR BEARING TRIP 0-199 C, OFF/32-390 F, OFF in 1 increments
(100)
5 MB A XXX MOTOR BEARING ALARM
0-199 C, OFF/32-390 F, OFF in 1 increments
(80)
6 LB T XXX LOAD BEARING TRIP
0-199 C, OFF/32-390 F, OFF in 1 increments
(80)
7 LB A XXX LOAD BEARING ALARM 0-199 C, OFF/32-390 F, OFF in 1 increments
(80)
8 AX T XXX AUXILIARY TRIP
0-199 C, OFF/32-390 F, OFF in 1 increments
(100)
9 AX A XXX AUXILIARY ALARM
0-199 C, OFF/32-390 F, OFF in 1 increments
(80)
10 DIAG ON
or
DIAG OFF
ALARM ON RTD FAILURE DIAGNOSTIC
Toggles between DIAG ON and DIAG OFF
PAGE 3, SP TRIP SETTINGS FOR TRIP EVENTS
1 GFT XXX GROUND FAULT TRIP LEVEL IN % OF
GROUND CT RATIO NUMERATOR
2-55% OF Ground CT ration numerator, OFF
(1% increments) (24%)
Program Date Control Schematic
Unit ID/Starter Type Work Order #
Motor HP Mfgr. Serial # Volts
FLA LRC Stall Time/LRT Accel. Time
SF RTD Type Other