EasyManua.ls Logo

Eaton MP-4000 - Page 22

Eaton MP-4000
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 4-8
www.eaton.com
IB02602002E MP-4000
Table 4-3. View Setting Mode/Program Worksheet.
SUB-
MENU
LINE # DISPLAY HELP MESSAGE SETTING RANGE/VALUE
(DEFAULT SELECTION AND
VALUE AS SHIPPED IN BOLD)
VALUE SELECTED
2 GFSD XX GROUND FAULT START DELAY IN
CYCLES
2-60 ac cycles (1 cycle increments) (5)
3 GFRD XX GROUND FAULT RUN DELAY IN CYCLES
0-60 ac cycles (1 cycle increments) (2)
4 IOC XXX INSTANTANEOUS OVERCURRENT IN
% FLA
300-1,600%, OFF (1% increments)
5 IOCSD XX INSTANTANEOUS OVERCURRENT
START DELAY IN CYCLES
2-60 ac cycles (1 cycle increments) (3)
6 JMT XXX JAM TRIP LEVEL IN % FLA
100-1,200%, OFF (1% increments) (1,000%)
7 JMSD XX JAM TRIP AND ALARM START DELAY IN
SECONDS
0-1,200 sec. (1 sec. increments) (60)
8 JMTR XX JAM TRIP RUN DELAY IN SECONDS
0-240 sec. (1 sec. increments) (60)
9 ULT XXX UNDERLOAD TRIP LEVEL IN % FLA
6-90%, OFF (1% increments)
10 ULSD XXX UNDERLOAD TRIP AND ALARM START
DELAY IN SECONDS
0-120 sec. (1 sec. increments) (10)
11 ULTR XXX UNDERLOAD TRIP RUN DELAY IN
SECONDS
0-240 sec. (1 sec. increments) (10)
12 UBT XXX PHASE UNBALANCE TRIP LEVEL
4-40%, OFF (1% increments)
13 UBSD XXX PHASE UNBALANCE TRIP AND ALARM
START DELAY IN SECONDS
0-120 sec. (1 sec. increments) (10)
14 UBTR XXX PHASE UNBALANCE TRIP RUN DELAY IN
SECONDS
0-240 sec. (1 sec. increments) (2)
PAGE 4, SP ALARM SETTINGS FOR ALARM EVENTS
1 GFA XXX GROUND FAULT ALARM LEVEL IN % OF
GROUND CT RATIO NUMERATOR
2-55% OF Ground CT ration numerator, OFF
(1% increments)
2 I2TA XXX I2T ALARM LEVEL IN % FULL OF I2T TRIP
CAPACITY
60-99%, OFF (1% increments) (80)
3 JMA XXX JAM ALARM LEVEL IN % FLA
100-1,200%, OFF (1% increments) (1,000%)
4 JMAR XXX JAM ALARM RUN DELAY IN SECONDS
0-240 sec. (1 sec. increments) (2)
5 ULA XXX UNDERLOAD ALARM LEVEL IN % FLA
6-90%, OFF (1% increments)
6 ULAR XXX UNDERLOAD ALARM RUN DELAY IN
SECONDS
0-240 sec. (1 sec. increments) (10)
7 UBA XXX PHASE UNBALANCE ALARM LEVEL
4-40%, OFF (1% increments) (10)
8 UBAR XXX PHASE UNBALANCE ALARM RUN DELAY
IN SECONDS
0-240 sec. (1 sec. increments) (10)
PAGE 5, SP START SETTINGS FOR START EVENTS
1 ST/T XXX STARTS PER TIME ALLOWED
1-10 starts/time (increments of 1) (1)
2 T/ST XXX TIME ALLOWED FOR STARTS COUNT IN
MINUTES
1-240 minutes, OFF (1 minute increments)
3 TBS XXX TIME BETWEEN STARTS IN MINUTES
1-240 minutes, OFF (1 minute increments)
4 NOCS X NUMBER OF COLD STARTS ALLOWED
1-5 starts (increments of 1) (1)
5 TRNC XXX MOTOR START TRANSITION CURRENT
LEVEL IN %FLA
10-300% (1% increments) (130)
6 TRNT XXX MOTOR START TRANSITION TIME IN
SECONDS
0-1,200 sec. (1 sec. increments) (10)
7 Choose:
TRN TIME
TRN I
TRN T+C
TRN T/C
TRANSITION ON EVENT
TRN TIME - ON TIME ONLY
TRN I - ON CURRENT ONLY
TRN T+C - ON TIME OR CURRENT
TRN T/C - ON TIME AND CURRENT
Choose one of the four conditions that determine
a start-to-run transition: TRN TIME, TRN I,
TRN T+C, or TRN T/C
Refer to settings P5L5 and P5L6.

Table of Contents

Related product manuals