Page 4-10
www.eaton.com
IB02602002E MP-4000
Table 4-3. View Setting Mode/Program Worksheet.
SUB-
MENU
LINE # DISPLAY HELP MESSAGE SETTING RANGE/VALUE
(DEFAULT SELECTION AND
VALUE AS SHIPPED IN BOLD)
VALUE SELECTED
5 Choose:
UB A ON
UB T ON
or
UB OFF
ENABLE PHASE UNBALANCE ALARM
OR TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between UB A ON, UB T ON, and
UB OFF
6 Choose:
WD A ON
WD T ON
or
WD OFF
ENABLE WINDING TEMP ALARM OR
TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between WD A ON, WD T ON, and
WD OFF
7 Choose:
MB A ON
MB T ON
or
MB OFF
ENABLE MOTOR BEARING ALARM OR
TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between MB A ON, MB T ON, and
MB OFF
8 Choose:
LB A ON
LB T ON
or
LB OFF
ENABLE LOAD BEARING ALARM OR
TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between LB A ON, LB T ON, and
LB OFF
9 Choose:
AX A ON
AX T ON
or
AX OFF
ENABLE AUXILIARY RTD TEMP ALARM
OR TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between AX A ON, AX T ON, and
AX OFF
10 Choose:
SX A ON
SX T ON
or
SX OFF
ENABLE STARTS PER TIME TRIP OR
ALARM TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between SX A ON, SX T on, and
SX OFF
11 Choose:
TBS T ON
or
TBS OFF
ENABLE TIME BETWEEN STARTS TRIP
TO ACTIVATE ALARM RELAY OUTPUT
OR DISABLE
Toggles between TBS T ON and TBS OFF
12 RTDF ON
or
RTDF OFF
ENABLE INDIVIDUAL RTD CHANNEL
FAILURE TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between RTDF ON and RTDF OFF
13 RCOM ON
or
RCOM OFF
ENABLE RTD MODULE
COMMUNICATION FAILURE TO
ACTIVATE ALARM RELAY OR DISABLE
Toggles between RCOM ON and RCOM OFF
14 IOCT ON
or
IOCT OFF
ENABLE INSTANTANEOUS TRIP TO
ACTIVATE ALARM RELAY OUTPUT
OR DISABLE
Toggles between IOCT ON and IOCT OFF
15 PH R ON
or
PH R OFF
ENABLE PHASE REVERSAL TRIP TO
ACTIVATE ALARM RELAY OUTPUT OR
DISABLE
Toggles between PH R ON and PH R OFF
16 INSQ ON
or
INSQ OFF
ENABLE INCOMPLETE SEQUENCE
TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between INSQ ON and INSQ OFF
17 REMT ON
or
REMT OFF
ENABLE REMOTE TRIP TO ACTIVATE
ALARM RELAY OUTPUT OR DISABLE
Toggles between REMT ON and REMT OFF
18 DIFT ON
or
DIFT OFF
ENABLE DIFFERENTIAL TRIP TO
ACTIVATE ALARM RELAY OUTPUT
OR DISABLE
Toggles between DIFT ON and DIFT OFF
19 INCT ON
or
INCT OFF
ENABLE INCOM TRIP TO ACTIVATE
ALARM RELAY OUTPUT OR DISABLE
Toggles between INCT ON and INCT OFF
20 TRNT ON
or
TRNT OFF
ENABLE TRANSITION TRIP TO
ACTIVATE ALARM RELAY OUTPUT
OR DISABLE
Toggles between TRNT ON and TRNT OFF
21 ZSWT ON
or
ZSWT OFF
ENABLE ZERO SPEED SWITCH TRIP
TO ACTIVATE ALARM RELAY OUTPUT
OR DISABLE
Toggles between ZSWT ON and ZSWT OFF
22 TBYP ON
or
TBYB OFF
ENABLE TRIP BYPASS TO ACTIVATE
ALARM RELAY OUTPUT OR DISABLE
Toggles between TBYP ON and TBYP OFF

Table of Contents