Page 4-20
www.eaton.com
IB02602002E MP-4000
Table 4.4 History Mode Display.
PAGE LINE DISPLAY COMPLETE HELP MESSAGE DESCRIPTION
HIST
MTR
HISTORY OF MOTOR STATISTICS
OCNT XX OCNT XX OPERATION COUNT SINCE LAST
RESET
Number of motor starts logged since last reset.
MM/DD/YY DATE OF RESET Date when OCNT was reset.
HH:MM:SS TIME OF RESET Time when OCNT was reset.
RT XXXX RT XXXX RUN TIME IN HOURS SINCE LAST
RESET
Total motor run time accumulated since last
reset.
MM/DD/YY DATE OF RESET Date when RT was reset.
HH:MM:SS TIME OF RESET Time when RT was reset.
IMS XXXX IMS XXXX HIGHEST STARTING PHASE CURRENT Highest starting phase current monitored since last reset.
MM/DD/YY DATE OF EVENT Date of highest IMS.
HH:MM:SS TIME OF EVENT Time of highest IMS.
IMR XXXX IMR XXXX HIGHEST RUNNING PHASE CURRENT Highest running phase current monitored since last reset.
MM/DD/YY DATE OF EVENT Date of highest IMR.
MM/DD/YY TIME OF EVENT Time of highest IMR.
UBM XXX UBM XXX HIGHEST PHASE UNBALANCE Maximum phase unbalance monitored since last reset.
MM/DD/YY DATE OF EVENT Date of highest phase unbalance.
HH:MM:SS TIME OF EVENT Time of highest phase unbalance.
WMX XXXX WMX XXXX HIGHEST MOTOR WINDING
TEMPERATURE IN DEGREES C (F)
Maximum motor winding temperature monitored since last reset.
MM/DD/YY DATE OF EVENT Date of highest WMX.
HH:MM:SS TIME OF EVENT Time of highest WMX.
MBX XXXX MBX XXXX HIGHEST MOTOR BEARING
TEMPERATURE IN DEGREES C (F)
Maximum motor bearing temperature monitored
since last reset.
MM/DD/YY DATE OF EVENT Date of highest MBX.
HH:MM:SS TIME OF EVENT Time of highest MBX.
LBX XXXX LMX XXXX HIGHEST LOAD BEARING
TEMPERATURE IN DEGREES C (F)
Maximum load bearing temperature monitored since last reset.
MM/DD/YY DATE OF EVENT Date of highest LMX.
HH:MM:SS TIME OF EVENT Time of highest LMX.
EMOR XXX EMOR XXX NUMBER OF EMERGENCY OVERRIDES
SINCE LAST RESET
Total number of emergency overrides performed since reset.
MM/DD/YY DATE OF RESET Date EMOR was reset.
HH:MM:SS TIME OF RESET Time EMOR was reset.
VUM XXXX VUM XXXX HIGHEST VOLTAGE UNBALANCE SINCE
LAST RESET
Time stamped maximum voltage unbalance since last reset.
MM/DD/YY DATE OF RESET Date when VMU was reset.
HH:MM:SS TIME OF RESET Time when VMU was reset.
VPL XXXX VPL LOWEST RUNNING PHASE VOLTAGE
SINCE LAST RESET
Lowest run time phase voltage since last reset.
MM/DD/YY DATE OF RESET Date when VPL was reset.
HH:MM:SS TIME OF RESET Time when VPL was reset.
VPM XXXX VPM XXXX HIGHEST PHASE VOLTAGE SINCE LAST
RESET
MM/DD/YY DATE OF RESET Date when VPM was reset.
HH:MM:SS TIME OF RESET Time when VPM was reset.
HIST TRP HISTORY OF TRIP EVENTS
GF T XX GF T XX NUMBER OF GROUND FAULT TRIPS
SINCE LAST RESET
Total number of respective trips that occurred
since reset.
MM/DD/YY DATE OF RESET Date when respective trip function was reset.
HH:MM:SS TIME OF RESET Time when respective trip function was reset.