www.eaton.com Page 4-19
MP-4000 IB02602002E
Table 4-3. View Setting Mode/Program Worksheet.
SUB-
MENU
LINE # DISPLAY HELP MESSAGE SETTING RANGE/VALUE
(DEFAULT SELECTION AND
VALUE AS SHIPPED IN BOLD)
VALUE SELECTED
6 Choose:
UP A ON
UP T ON
UP OFF
ENABLE UNDERPOWER ALARM OR
TRIP TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between UP T ON, UP A ON, UP OFF
7 Choose:
PF A ON
PF T ON
PF OFF
ENABLE POWER FACTOR ALARM OR
TRIP TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between PF T ON, PF A ON, PF OFF
PAGE 24, SP2 AUX2 SETTINGS FOR AUX 2 RELAY OUTPUT CONFIGURATION
1 Choose:
VU A ON
VU T ON
VU OFF
ENABLE VOLTAGE UNBALANCE ALARM
OR TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between VUT ON, VUA ON, VU OFF
2 Choose:
OV A ON
OV T ON
OV OFF
ENABLE OVERVOLTAGE ALARM OR
TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between OVT ON, OVA ON, OV OFF
3 Choose:
UV A ON
UV T ON
UV OFF
ENABLE UNDERVOLTAGE ALARM OR
TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between UVT ON, UVA ON, UV OFF
4 Choose:
OF A ON
OF T ON
OF OFF
ENABLE OVERFREQUENCY ALARM
OR TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between OF T ON, OF A ON, OF OFF
5 Choose:
UF A ON
UF T ON
UF OFF
ENABLE UNDERFREQUENCY ALARM
OR TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between UF T ON, UF A ON, UF OFF
6 Choose:
UP A ON
UP T ON
UP OFF
ENABLE UNDERPOWER ALARM OR
TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
Toggles between UP T ON, UP A ON, UP OFF
7 Choose:
PF A ON
PF T ON
PF T OFF
ENABLE POWER FACTOR ALARM OR
TRIP TO ACTIVATE AUX2 RELAY OUTPUT
OR DISABLE
Toggles between PF T ON, PF A ON, PF OFF
PAGE 25, SP2 SYS SETTINGS FOR SYSTEM CONFIGURATION
1 WH XXX SETTING FOR ACTIVE ENERGY WATT-
HOUR DISPLAY - NORMAL OR KILO OR
GIGA
Select KILO, MEGA, or GIGA
2 VARH XX SETTING FOR REACTIVE ENERGY
VARH DISPLAY - NORMAL OR KILO OR
GIGA
Select KILO, MEGA, or GIGA
3 VAH XXX SETTING FOR APPARENT ENERGY VAH
DISPLAY - NORMAL OR KILO OR GIGA
Select KILO, MEGA, or GIGA
4 WATT XXX SETTING FOR ACTIVE POWER WATT
DISPLAY - NORMAL OR KILO OR MEGA
Select NORMAL, KILO, or MEGA
5 VAR XXX SETTING FOR REACTIVE POWER VAR
DISPLAY - NORMAL OR KILO OR MEGA
Select NORMAL, KILO, or MEGA
6 VA XXX SETTING FOR APPARENT POWER VA
DISPLAY - NORMAL OR KILO OR MEGA
Select NORMAL, KILO, or MEGA
7 PTR XXX RATIO OF EXTERNAL PT
1 - 250:1, 0.01 increments (34.6)
8 XFMR XXX XFMR CONFIGURATION - SELECT -
WYE, DELTA, OPEN DELTA
Select 0 = WYE, 1= DELTA, 2 = OPEN
DELTA
9 VOLT XXX SETTING FOR VOLTAGE DISPLAY -
VOLTS OR KILO VOLTS
Select VOLTS or KILOVOLTS
PAGE 26, SP COMM SETTINGS FOR RS-232 COMMUNICATIONS
1 232 XXX RS232 COMMUNICATION - ON OR OFF Select RS-232 communications, either ON or
OFF