Page 4-18
www.eaton.com
IB02602002E MP-4000
Table 4-3. View Setting Mode/Program Worksheet.
SUB-
MENU
LINE # DISPLAY HELP MESSAGE SETTING RANGE/VALUE
(DEFAULT SELECTION AND
VALUE AS SHIPPED IN BOLD)
VALUE SELECTED
9 LGPFE XXXX LAGGING POWER FACTOR ALARM
ENABLE OR DISABLE
Power factor (55) alarm enable or disable select
lagging (ON)
10 PFLGA XXXX LAGGING POWER FACTOR ALARM
THRESHOLD
Power factor alarm threshold range from
0.05 - 0.99 lagging, 0.01 increments (0.90)
11 PFAS XXXX POWER FACTOR ALARM START DELAY
Power factor alarm start delay 0- 60 sec.,
100 msec. increments
12 PFAR XXXX POWER FACTOR ALARM RUN DELAY
Power factor alarm run delay 0 - 60 sec ,
100 msec. increments
PAGE 22, SP2 AREL SETTINGS FOR ALARM RELAY OUTPUT CONFIGURATION
1 Choose:
VU T ON
VU A ON
VU OFF
ENABLE VOLTAGE UNBALANCE ALARM
OR TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between VUT ON, VUA ON, VU OFF
2 Choose:
OV T ON
OV A ON
OV OFF
ENABLE OVERVOLTAGE ALARM OR
TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between OVT ON, OVA ON, OV OFF
3 Choose:
UV T ON
UV A ON
UV OFF
ENABLE UNDERVOLTAGE ALARM OR
TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between UVT ON, UVA ON, UV OFF
4 Choose:
OFT ON
OFA ON
OF OFF
ENABLE OVERFREQUENCY ALARM OR
TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between OF T ON, OF A ON, OF OFF
5 Choose:
UF T ON
UF A ON
UF OFF
ENABLE UNDERFREQUENCY ALARM
OR TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between UF T ON, UF A ON, UF OFF
6 Choose:
UP T ON
UP A ON
UP OFF
ENABLE UNDERPOWER ALARM OR
TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between UP T ON, UP A ON, UP OFF
7 Choose:
PF T ON
PF A ON
PF OFF
ENABLE POWER FACTOR ALARM OR
TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
Toggles between PF T ON, PF A ON, PF OFF
PAGE 23, SP2 AUX1 SETTINGS FOR AUX 1 RELAY OUTPUT CONFIGURATION
1 Choose:
VU A ON
VU T ON
VU OFF
ENABLE VOLTAGE UNBALANCE ALARM
OR TRIP TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between VUT ON, VUA ON, VU OFF
2 Choose:
OV A ON
OV T ON
OV OFF
ENABLE OVERVOLTAGE ALARM OR
TRIP TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between OVT ON, OVA ON, OV OFF
3 Choose:
UV A ON
UV T ON
UV OFF
ENABLE UNDERVOLTAGE ALARM OR
TRIP TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between UVT ON, UVA ON, UV OFF
4 Choose:
OF A ON
OF T ON
OF OFF
ENABLE OVERFREQUENCY ALARM
OR TRIP TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between OF T ON, OF A ON, OF OFF
5 Choose:
UF A ON
UF T ON
UF OFF
ENABLE UNDERFREQUENCY ALARM
OR TRIP TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
Toggles between UF T ON, UF A ON, UF OFF