www.eaton.com Page 4-17
MP-4000 IB02602002E
Table 4-3. View Setting Mode/Program Worksheet.
SUB-
MENU
LINE # DISPLAY HELP MESSAGE SETTING RANGE/VALUE
(DEFAULT SELECTION AND
VALUE AS SHIPPED IN BOLD)
VALUE SELECTED
5 OVA XXXX OVERVOLTAGE MAIN ALARM
THRESHOLD
Main over voltage alarm (59 M-2) 10 - 150 V
or OFF
6 OVARXXXX.X OVERVOLTAGE MAIN ALARM RUN
DELAY
Main over voltage alarm (59 M-2) time delay
0 - 480 sec., (0.1 sec. increments)
7 OVNT XXXX OVERVOLTAGE NEUTRAL TRIP
THRESHOLD SETTING FOR
UNDERVOLTAGE
Neutral over voltage trip (59 N-1) threshold
10 - 150 V, or OFF
PAGE 19, SP UVTRP SETTINGS FOR UNDER VOLTAGE
1 UVPT XXXX UNDERVOLTAGE TRIP PICKUP
CRITERION - SELECT -
1 - ANY PHASE
2 - ANY TWO PHASES
3 - ALL THREE PHASES
Under voltage (27 M-1) pickup criterion 1 to 3
phases
2 UVT XXXX MAIN UNDERVOLTAGE TRIP
THRESHOLD
Under voltage (27 M-1) threshold 10 - 150 V,
increments 1 V or OFF
3 UVTR XXXX MAIN UNDERVOLTAGE TRIP RUN
DELAY
Under voltage (27 M-1) trip run delay 0 - 60 sec.,
increments .1 sec. on mains
4 UVPA XXXX UNDERVOLTAGE ALARM PICKUP
CRITERION - SELECT -
1 - ANY PHASE
2 - ANY TWO PHASES
3 - ALL THREE PHASES
Under voltage (27 M-2) pickup criterion 1 - 3
phases
5 UVA XXXX MAIN UNDERVOLTAGE ALARM
THRESHOLD
Under voltage (27 M-2) threshold 10 - 150 V, or
disabled, 1 V increments on mains (OFF)
6 UVAR XXXX MAIN UNDERVOLTAGE ALARM RUN
DELAY
Under voltage (27 M-2) run delay 0 - 60 sec.,
0.1 sec. increments
7 UVSD XXXX UNDER VOLTAGE TRIP AND ALARM
START DELAY
Under voltage trip & alarm start delay 0 - 60 sec.,
0.1 sec. increments
PAGE 20, SP UPTRP SETTINGS FOR UNDER POWER
1 UPT XXXX UNDERPOWER TRIP THRESHOLD Under power (32) trip threshold 0.06 - 0.90 *FLA
*VT, or disable (OFF)
2 UPTR XXXX UNDERPOWER TRIP RUN DELAY
Under power trip run delay 0 - 480 sec. ( 0.1
sec.)
3 UPA XXXX UNDERPOWER ALARM THRESHOLD Under power (32) alarm threshold 0.06 - 0.90
*FLA *VT, or disable (OFF)
4 UPAR XXXX UNDERPOWER ALARM RUN DELAY
Under power alarm run delay (0)
5 UPSD XXXX UNDERPOWER TRIP AND ALARM START
DELAY
Under power trip start delay 0- 60 sec.
PAGE 21, SP PFTRP SETTINGS FOR POWER FACTOR
1 PFLDE XXXX LEADING POWER FACTOR TRIP
ENABLE OR DISABLE
Power factor (55) ON or OFF select
2 PFLDT XXXX LEADING POWER FACTOR TRIP
THRESHOLD
Power factor trip threshold range from
(0.05 - 0.99) leading, 0.01 increments (.90)
3 PFLGE XXXX LAGGING POWER FACTOR TRIP
ENABLE OR DISABLE
Power factor (55) ON or OFF select
4 PFLGT XXXX LAGGING POWER FACTOR TRIP
THRESHOLD
Power factor trip threshold range from 0.05 - 0.99
lagging, 0.01 increments (0.90)
5 PFTS XXXX POWER FACTOR TRIP START DELAY Power factor start delay 0 - 60 sec., 100 msec.
increments
6 PFTR XXXX POWER FACTOR TRIP RUN DELAY
Power factor trip run delay 0 - 60 sec., 100 msec.
increments
7 LDPFE XXXX LEADING POWER FACTOR ALARM
ENABLE OR DISABLE
Power factor (55) alarm enable or disable select,
leading (ON)
8 PFLDA XXXX LEADING POWER FACTOR ALARM
THRESHOLD
Power factor alarm threshold range from
0.05 - 0.99 leading, 0.01 increments (.90)