Page 4-16
www.eaton.com
IB02602002E MP-4000
Table 4-3. View Setting Mode/Program Worksheet.
SUB-
MENU
LINE # DISPLAY HELP MESSAGE SETTING RANGE/VALUE
(DEFAULT SELECTION AND
VALUE AS SHIPPED IN BOLD)
VALUE SELECTED
8 ENG RST
or
PUSH RST
ENG RST - PUSH RAISE TO ENABLE
ENERGY RESET
PUSH RST - PUSH RESET TO EXECUTE
RESET OF ENERGY OR PUSH RAISE TO
NOT RESET
Change to PUSH RST and press Reset button,
or
return to ENG RST (none)
Page 15, SP VUTRP SETTINGS FOR VOLTAGE UNBALANCE
1 VPNT XXXX V1,V2 TRIP THRESHOLD Phase Unbalance (47-1) V1 Trip threshold
1 to 100 V in 1 V increments (50)
2 VUT XXXX RATIO OF V2 TO V1 TRIP THRESHOLD
4% - 40%, off 1% increments (OFF)
3 VUSD XXXX VOLTAGE PHASE UNBALANCE TRIP AND
ALARM START DELAY
Phase Unbalance Trip & Alarm Start Delay
0-480 sec., 1 sec. increments (0)
4 VUTR XXXX VOLTAGE PHASE UNBALANCE TRIP
RUN DELAY
47-1 Phase Unbalance Run Delay
1 to 480 sec. (1 sec. steps) (1 sec)
5 VPNA XXXX V1,V2 ALARM THRESHOLD Phase Unbalance. (47-2) V2 Alarm threshold
1 to 100 V, 1 V increments (50)
6 VUA XXXX RATIO OF V2 TO V1 ALARM
THRESHOLD
4% - 40%, off 1% increments (ON)
7 VUAR XXXX VOLTAGE PHASE UNBALANCE ALARM
RUN DELAY
47-2 Phase unbalance Run delay 1 to 480 sec.
(1 sec. steps) (1)
Page 16, SP UFTRP SETTINGS FOR UNDER FREQUENCY
1 UFT XXXX UNDERFREQUENCY TRIP THRESHOLD Under Frequency Trip Threshold 15 to 60,
0.01 Hz increments, OFF
2 UFSD XXXX UNDERFREQUENCY TRIP AND ALARM
START DELAY
Under Frequency Trip / Alarm Start delay
0-60 sec.) 0.1 sec. increments
3 UFTR XXXX UNDERFREQUENCY TRIP RUN DELAY
Under Frequency Time Delay 0-60 sec., 0.1 sec.
increments
4 UFA XXXX UNDERFREQUENCY ALARM
THRESHOLD
Under Frequency Threshold 15 - 60 Hz, 0.01 Hz
increments, OFF
5 UFAR XXXX UNDERFREQUENCY ALARM RUN
DELAY SETTINGS FOR
OVERFREQUENCY
Under Frequency Time Delay 0-60 sec.,
0.1 sec. increments
Page 17, SP OFTRP SETTINGS FOR OVERFREQUENCY
1 OFT XXXX OVERFREQUENCY TRIP THRESHOLD Over Frequency Trip Threshold 15 to 70,
0.1 sec. increments, OFF
2 OFSD XXXX OVERFREQUENCY TRIP AND ALARM
START DELAY
Over Frequency Trip / Alarm Start Delay
0-60 sec.
3 OFTR XXXX OVERFREQUENCY TRIP RUN DELAY
Over Frequency Trip Time Delay 0-60 sec,
0.1 sec. increments
4 OFA XXXX OVERFREQUENCY ALARM
THRESHOLD
Over Frequency Alarm Threshold 15-70 sec.,
0.1 sec. increments, OFF
5 OFAR XXXX OVERFREQUENCY ALARM RUN
DELAY
Over Frequency Alarm Time Delay 0-60 sec.,
0.1 sec. increments
PAGE 18, SP SP OVTRP SETTINGS FOR OVER VOLTAGE
1 OVPT XXXX OVERVOLTAGE TRIP PICKUP
CRITERION - SELECT -
1 - ANY PHASE
2 - ANY TWO PHASES
3 - ALL THREE PHASES
Over voltage 59 M-1 on 1 to 3 phases trip
2 OVT XXXX OVERVOLTAGE MAIN TRIP THRESHOLD Main over voltage 59 M-1 trip threshold
10 to 150 V (1 V increments) OFF
3 OVTRXXXX.X OVERVOLTAGE MAIN TRIP RUN DELAY Main over voltage 59 M-1 delay 0 to 480 sec.
(100 msec. increments)
4 OVPA XXXX OVERVOLTAGE ALARM PICKUP
CRITERION - SELECT -
1 - ANY PHASE
2 - ANY TWO PHASES
3 - ALL THREE PHASES
Over voltage 59 M-2 on 1 to 3 phases alarm