Eaton 5125 Rack-Mount UPS (5000/6000 VA) User's Guide S 164201541 Rev D
www.eaton.com/powerquality
43
Chapter 5 Configuration
When the UPS is in Configuration mode, the front panel LEDs represent
the configuration options. Use the control buttons (On
button,
Off
button, and button) to modify the UPS configuration.
Figure 21 shows the LEDs and Table 2 explains the corresponding
options.
To reconfigure the UPS default settings:
1. Press and hold the On
button and the button simultaneously
for three seconds. The UPS transfers to Configuration mode.
The LEDs flash briefly and then display the enabled options.
NOTE If the LEDs start cycling automatically from left to right, repeat Step 1 and be sure to
press both buttons.
2. Press the On button to scroll through the options. Each time you
press the button, the UPS beeps. The LED for the selected option
indicates the current setting; flashing represents disabled options
(see Figure 21 and Table 2).
Scrolling past the last LED returns to the first configuration option.
If you press the On
button and nothing happens, the UPS is still in
Operation mode. Repeat Step 1 to enter Configuration mode, and
then perform Step 2.
3. Press the Off
button ONCE to select the Voltage or Extended
Battery Module (EBM) option or to toggle the Site Wiring Fault
Alarm on or off.
NOTE The UPS exits Configuration mode automatically after two minutes of inactivity.
4. Press the button to confirm the selection and exit Configuration
mode. If you do not press the
button, the UPS defaults to the
original settings.