CONFIGURATION
Eaton 5125 Rack-Mount UPS (5000/6000 VA) User's Guide S 164201541 Rev D
www.eaton.com/powerquality
45
ExplanationLED StatusOption
Configuration Mode
LEDs
Site Wiring
Fault Alarm
On Alarm sounds when the polarity of the outlet is reversed or the
ground connection is missing; have a qualified electrician
repair the outlet wiring.
Flashing
(default)
Alarm DOES NOT sound when the polarity of the outlet is
reversed or the ground connection is missing.
0 EBMs
On
(default)
Zero EBMs are configured.
Flashing One of the other EBM configurations is selected.
1 EBM
On One EBM is configured.
Flashing One of the other EBM configurations is selected.
2 EBMs
On Two EBMs are configured.
Flashing One of the other EBM configurations is selected.
3 EBMs
On Three EBMs are configured.
Flashing One of the other EBM configurations is selected.
4 EBMs
On Four EBMs are configured.
Flashing One of the other EBM configurations is selected.