OPERATION
EATON Powerware
®
9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev F www.powerware.com
60
Table 9. User Settings (continued)
Default SettingAvailable SettingsDescription
Set Nominal Output Voltage 120V/240V
120V/208V
110V/220V
100V/200V
127V/220V
120V/208V
Bypass Voltage High Limit +1 through +20% (1% increments) 120V +10%
Bypass Voltage Low Limit -1 through -20% (1% increments) 120V -15%
Nominal Output Frequency 50 Hz or 60 Hz 60 Hz
Synchronization Enabled/Disabled Enabled
Synchronization Window ±0.5 through ±3.0 Hz (0.1 Hz increments) ±2.0 Hz
Unsynchronized Transfer to Bypass Allowed/Not Allowed Not Allowed
Output Frequency Slew Rate 0.1 though 5 hertz per second
(0.1 Hz increments)
0.5 Hz/s
Usage of Bypass Enabled/Disabled Enabled
Transfer to Bypass When Overload After a delay/Immediately After a delay
Automatic Start Delay -1 through 32767 seconds
(-1 m eans disabled)
0s
Control Commands from X-Slot1 Allowed/Disabled Allowed
Control Commands from X-Slot2/Serv Allowed/Disabled Allowed
X-Slot Signal Input Activation Delay 0 through 65 seconds 5s
Input signal delayed shutdown delay 1 through 65535 seconds 120s
Site Wiring Fault Notice Enabled/Disabled Enabled
Reset Custom Event Settings 0 through 32 Total: 0/32
Auto Output Configuration Enabled/Disabled Enabled for initial startup
Disabled after initial startup