Chapter 6—Installation requirements
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
Power wiring notice
Do not discard the plastic bag containing the wiring
hardware.
1. Remove the A-cover by removing (4) screws, then lifting
the A-cover away from the base
Wiring hardware contents (included with drive)
•
European rubber grommet and flat rubber grommet
(for IP54 integrity)
•
Modification label
•
Detachable cable clamp
•
Attachable grounding strap
•
Ground strap mounting screws
Power wiring/grounding
2. Remove power wiring protection plate. Use power/motor
cable tables on Appendix B
3. Add attachable grounding clamps (qty 2), one on each
side of drive
4. Pass motor, input power wires/cables through base
wiring plate
5. If shielded cable is used, connect the shields of input
power and motor cables shields to ground
6. Wire power terminals (L1, L2, L3), motor terminal
(U, V, W), and grounding terminals per Figure 24.
Itis recommended for power and motor leads to be in
separate conduit
To meet the UL requirements, if conduit is being used
for wiring, the enclosure openings provided for conduit
connections in the field shall be closed by UL listed
conduit fittings with the same type rating (Type 1/
Type12) as the enclosure.