21
Chapter 3—Product overview
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
Maintenance and inspection
PowerXL frequency inverters are maintenance free.
However,external influences may affect the function
and the lifespan of the PowerXL frequency inverter. We
therefore recommend that the devices are checked regularly
and the following maintenance measures are carried out at
thespecifiedintervals.
If the PowerXL frequency inverter is damaged by external
influences, contact Technical Service.
Table 25. Maintenance measures and intervals
Maintenance measure Maintenance interval
Clean cooling vents (cooling slits) If required
Check the fan function 6–24 months (depending on
the environment)
Filter in the switching cabinet doors
(see manufacturer specifications)
6–24 months (depending on
the environment)
Check the tightening torques of the terminals
(control signal terminals, power terminals)
Regularly
Check connection terminals and all metallic
surfaces for corrosion
6–24 months (depending on
the environment)
Storage
If the frequency inverter is stored before use, suitable
ambient conditions must be ensured at the site of storage:
Storage temperature: –40 °F to 158 °F (–40 °C to 70 °C)
Relative average air humidity: <95%, noncondensing
(EN 50178)
To prevent damage to the DC link capacitors, storage
times longer than 12 months are not recommended
Charging the internal DC link capacitors
After extended storage times or extended downtimes
during which no power is supplied (>12 months), the
capacitors in the internal DC link must be recharged in a
controlled manner in order to prevent damage. To do this,
the PowerXL variable frequency drive must be supplied
with power, with a controlled DC power supply unit, via
two mains DC bus connection terminals. Please consult
thefactory for detailed instructions.
Service and warranty
In the unlikely event that you have a problem with your
PowerXL frequency inverter, please contact your local
salesoffice.
When you call, have the following information ready:
the exact frequency inverter part no. (see nameplate)
the date of purchase
a detailed description of the problem that has occurred
with the frequency inverter
If some of the information printed on the nameplate is not
legible, please state only the information that is clearly
legible. This information can also be found on the cover of
the control terminals.
Information concerning the guarantee can be found in the
General Terms and Conditions of Sale.