EasyManua.ls Logo

Eaton PowerXL DH1 - Field Wiring; Table 80. Protection Ratings-575 V Drive Series

Eaton PowerXL DH1
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
94
Appendix D—Safety instructions for UL and cUL
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
575 V Drive Series are suitable for use on a circuit capable of
delivering not more than 100,000 rms symmetrical amperes,
600 volts maximum, when protected by UL and cUL/CSA
Listed devices mentioned below with an A.I.C. rating of
100kA minimum.
Class RK5, Class J, Class T or equivalent fuses
Thermal-magnetic circuit breakers (see Note below)
Current limiting circuit breakers (for FR1-3 only)
ote: N When protected by UL and cUL/CSA Listed
Thermal-magnetic circuit breakers:
FR0–3 are only suitable for use on a circuit capable
of delivering not more than 35,000 rms symmetrical
amperes, 600 volts maximum
FR4–6 are only suitable for use on a circuit capable
of delivering not more than 65,000 rms symmetrical
amperes, 600 volts maximum
Refer to the following information for recommended ratings.
See Table 78.
Table 80. Protection ratings—575 V drive series
Frame
size
DG1
catalog number
DH1
catalog number
Maximum
fuse rating
Maximum
thermal-magnetic
breaker rating
Maximum current
limiting breaker
ratings
1 DG1-353D3xx-xxxx DH1-354D5XX-CXXC 600 V, 10 A 600 V, 15 A 600 V, 15 A
DG1-354D5xx-xxxx DH1-357D5XX-CXXC 600 V, 20 A 600 V, 20 A 600 V, 20 A
DG1-357D5xx-xxxx DH1-35010XX-CXXC 600 V, 30 A 600 V, 30 A 600 V, 30 A
2 DG1-35010xx-xxxx DH1-35013XX-CXXC 600 V, 35 A 600 V, 35 A 600 V, 35 A
DG1-35013xx-xxxx DH1-35018XX-CXXC 600 V, 60 A 600 V, 60 A 600 V, 60 A
DG1-35018xx-xxxx DH1-35022XX-CXXC 600 V, 80 A 600 V, 80 A 600 V, 80 A
3 DG1-35022xx-xxxx DH1-35027XX-CXXC 600 V, 80 A 600 V, 90 A 600 V, 90 A
DG1-35027xx-xxxx DH1-35034XX-CXXC 600 V, 80 A 600 V, 100 A 600 V, 100 A
DG1-35034xx-xxxx DH1-35041XX-CXXC 600 V, 80 A 600 V, 150 A 600 V, 150 A
4 DG1-35041xx-xxxx DH1-35052XX-CXXC 600 V, 150 A 600 V, 175 A N/A
DG1-35052xx-xxxx DH1-35062XX-CXXC 600 V, 150 A 600 V, 200 A N/A
DG1-35062xx-xxxx DH1-35080XX-CXXC 600 V, 150 A 600 V, 300 A N/A
5 DG1-35080xx-xxxx DH1-35100XX-CXXC 600 V, 200 A 600 V, 225 A N/A
DG1-35100xx-xxxx DH1-35125XX-CXXC 600 V, 200 A 600 V, 225 A N/A
DG1-35125xx-xxxx DH1-35144XX-CXXC 600 V, 200 A 600 V, 300 A N/A
6 DG1-35144xx-xxxx DH1-35208XX-CXXC 600 V, 400 A 600 V, 400 A N/A
DG1-35208xx-xxxx DH1-35250XX-CXXC 600 V, 400 A 600 V, 400 A N/A
otes: N These ratings are based off the largest wire size designed for the given Frame. Please verify your
protectionprotects your wire sizing. See Appendix B for recommended fuse and wire size.
IP20 FR0 will be available in June 2018.
Field wiring
The field installed conductors for this drive should be
75°C or higher copper wire
The enclosure openings provided for conduit connections
in the field shall be closed by UL Listed conduit fittings
with same type rating as the enclosure (Type 1/Type 12)

Table of Contents