94
Appendix D—Safety instructions for UL and cUL
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
575 V Drive Series are suitable for use on a circuit capable of
delivering not more than 100,000 rms symmetrical amperes,
600 volts maximum, when protected by UL and cUL/CSA
Listed devices mentioned below with an A.I.C. rating of
100kA minimum.
•
Class RK5, Class J, Class T or equivalent fuses
•
Thermal-magnetic circuit breakers (see Note below)
•
Current limiting circuit breakers (for FR1-3 only)
ote: N When protected by UL and cUL/CSA Listed
Thermal-magnetic circuit breakers:
•
FR0–3 are only suitable for use on a circuit capable
of delivering not more than 35,000 rms symmetrical
amperes, 600 volts maximum
•
FR4–6 are only suitable for use on a circuit capable
of delivering not more than 65,000 rms symmetrical
amperes, 600 volts maximum
Refer to the following information for recommended ratings.
See Table 78.
Table 80. Protection ratings—575 V drive series
Frame
size
DG1
catalog number
DH1
catalog number
Maximum
fuse rating
Maximum
thermal-magnetic
breaker rating
Maximum current
limiting breaker
ratings
1 DG1-353D3xx-xxxx DH1-354D5XX-CXXC 600 V, 10 A 600 V, 15 A 600 V, 15 A
DG1-354D5xx-xxxx DH1-357D5XX-CXXC 600 V, 20 A 600 V, 20 A 600 V, 20 A
DG1-357D5xx-xxxx DH1-35010XX-CXXC 600 V, 30 A 600 V, 30 A 600 V, 30 A
2 DG1-35010xx-xxxx DH1-35013XX-CXXC 600 V, 35 A 600 V, 35 A 600 V, 35 A
DG1-35013xx-xxxx DH1-35018XX-CXXC 600 V, 60 A 600 V, 60 A 600 V, 60 A
DG1-35018xx-xxxx DH1-35022XX-CXXC 600 V, 80 A 600 V, 80 A 600 V, 80 A
3 DG1-35022xx-xxxx DH1-35027XX-CXXC 600 V, 80 A 600 V, 90 A 600 V, 90 A
DG1-35027xx-xxxx DH1-35034XX-CXXC 600 V, 80 A 600 V, 100 A 600 V, 100 A
DG1-35034xx-xxxx DH1-35041XX-CXXC 600 V, 80 A 600 V, 150 A 600 V, 150 A
4 DG1-35041xx-xxxx DH1-35052XX-CXXC 600 V, 150 A 600 V, 175 A N/A
DG1-35052xx-xxxx DH1-35062XX-CXXC 600 V, 150 A 600 V, 200 A N/A
DG1-35062xx-xxxx DH1-35080XX-CXXC 600 V, 150 A 600 V, 300 A N/A
5 DG1-35080xx-xxxx DH1-35100XX-CXXC 600 V, 200 A 600 V, 225 A N/A
DG1-35100xx-xxxx DH1-35125XX-CXXC 600 V, 200 A 600 V, 225 A N/A
DG1-35125xx-xxxx DH1-35144XX-CXXC 600 V, 200 A 600 V, 300 A N/A
6 DG1-35144xx-xxxx DH1-35208XX-CXXC 600 V, 400 A 600 V, 400 A N/A
DG1-35208xx-xxxx DH1-35250XX-CXXC 600 V, 400 A 600 V, 400 A N/A
otes: N These ratings are based off the largest wire size designed for the given Frame. Please verify your
protectionprotects your wire sizing. See Appendix B for recommended fuse and wire size.
IP20 FR0 will be available in June 2018.
Field wiring
•
The field installed conductors for this drive should be
75°C or higher copper wire
•
The enclosure openings provided for conduit connections
in the field shall be closed by UL Listed conduit fittings
with same type rating as the enclosure (Type 1/Type 12)