10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.1 EtherNet/IP
PXR Electronic trip unit 01/21 MN012005EN www.eaton.com 101
The following instances are assigned to the data objects.
Table 53: Event summary - EtherNet/IP
Table 54: Historical trip / major alarm event - EtherNet/IP
Instance
Format R/W Description (historical event overview)
316 Encoded R/W Event type: summary = 0x8EFF
317 Unsigned 32 R Earliest event ID
318 Unsigned 32 R Latest event ID
319 Unsigned 32 R/W Requested event ID
320 Unsigned 32 R Previous event ID
321 Unsigned 32 R Next event ID
322 Date/time R Date/time
323
Encoded R Data format:
0x0000, 0x0001, 0x0004, 0x0005, 0x0005, 0x0006
324
B0 R Valid bit of the object
325 Encoded R Cause of event:
00: boot process - time OK
01: download of the setpoint values
02: time has been adjusted
03: trip
04: alarm
05: test mode has been selected
06: exiting the test mode
08: boot process - no time
09: test completed
10: maintenance mode activated
11: maintenance mode deactivated
12: opened via the communication interface
13: closed via the communication interface
Instance
Format R/W Description (historical event overview) Unit
316 Encoded R/W Event type:
Trip: 0x80FF
Alarm: 0x81FF
317
Unsigned 32 R Earliest event ID
318
Unsigned 32 R Latest event ID
319 Unsigned 32 R/W Requested event ID
320 Unsigned 32 R Previous event ID
321 Unsigned 32 R Next event ID
322 Date/time R Date/time
323 Encoded R Data format:
Trip: 0x0004
Main alarm: 0x0005
324 Bit 15 - Bit 0 R Valid bits of the object
325 Bit 31 - Bit 16 R Valid bits of the object
326 Encoded R Status reason (primary, secondary, reason)
327
Unsigned 32 R I
L1
(IA) A

Table of Contents