10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.1 EtherNet/IP
102 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
Table 55: Minor alarm event - EtherNet/IP
328 Unsigned 32 R I
L2
(IB) A
329 Unsigned 32 R I
L3
(IC) A
330
Unsigned 32 R I
N
(IN) A
332 Unsigned 32 R I
G
(IG residual) A
333 Unsigned 16 R U
L1-L2
(VAB) V
334 Unsigned 16 R U
L2-L3
(VBC) V
335 Unsigned 16 R U
L3-L1
(VCA) V
336 Unsigned 16 R U
L1-N
(VAN) V
337 Unsigned 16 R U
L2-N
(VBN) V
338 Unsigned 16 R U
L3-N
(VCN) V
339 Signed 32 R Active 3-phase power W
340 Signed 32 R Reactive 3-phase power VAR
341 Unsigned 32 R Apparent 3-phase power VA
342 Signed 32 R Active power demand W
343 Signed 32 R Reactive power demand VAR
344
Unsigned 32 R Apparent power demand VA
346 Unsigned 32 R Frequency 1/10 Hz
348 Unsigned 32 R Number of operations
349 Bit 31 - Bit 0 R Binary status with valid bits
Instance Format R/W Description (historical event overview)
316 Encoded R/W Event type:
Summary = 0x81FF
317
Signed 32 R Earliest event ID
318
Signed 32 R Latest event ID
319
Signed 32 R/W Requested event ID
320
Signed 32 R Previous event ID
321 Signed 32 R Next event ID
322 Date/time R Date/time
323 Encoded R Data format:
Small alarm: 0x0006
324
Bit 0 R Valid bits of the object
325 Encoded R Status reason (primary, secondary, reason code)
Instance Format R/W Description (historical event overview) Unit

Table of Contents

Related product manuals