10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.2 EtherCAT
118 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
In setting group 0, the maintenance mode setting (index 2008) can be
divided into two parts. The high byte is read only and is used for the status
indication of the maintenance mode, the comprehensive results of the
maintenance mode rotary switch, the secondary terminal and the
communication settings. The low byte can be configured and is used to
indicate the maintenance mode settings via the communication port.
The respective protection settings may vary according to the size, type and
rated operational current of the release.
200B 0 0x0001 Direction of inco-
ming supply
R/W Encoded 0: forward
1: reverse
Note:
only available on the PXR25
200C
0 0x0001 Sign convention R/W Encoded Sign convention:
0: IEC
1: IEEE
2: IEEE old
200D
Power demand
window
R/W Encoded Power demand:
0: fixed
1: sliding
200E Power demand
interval
R/W Encoded Power demand:
5 - 60 min (1 min increments)
2011
Configuration of
relay 1
R/W Encoded
Configuration of relay 1 and relay 2:
table 21, page 44
2012
Configuration of
relay 2
R/W Encoded
2014
Phase sequence -
phase L1 (A)
R/W Encoded Phase L1 (A)
0: counterclockwise
1: clockwise
2017
0xBCC Alarm - Residual
Life
R/W Encoded Range: 50 - 100, step size 1, default value: 75
Alarm level value 100 0 % residual life
Alarm level value 75 25 % residual life
Formula for conversion:
Alarm level expressed as a percentage
= 100 - point value