10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.2 EtherCAT
PXR Electronic trip unit 01/21 MN012005EN www.eaton.com 119
Table 67: Setting group 1: “Protection group“ - EtherCAT
Index
[Hex]
Bit
field
Mask
field
Setpoint name R/W Format Description or value Unit
2002 15 - 0 0xFFFFFF Password W Encoded 0000 (default setting)
2003 15 - 0 0xFFFFFF Group 1 = protec-
tion
R/W
2004
12 - 0 0x1FFFF Rated current R Encoded NZM2: 25, 40, 63, 90, 100, 140, 160, 200, 220,
250, 300
NZM3: 250, 350, 400, 450, 600, 630
NZM4: 550, 600, 630, 800, 875, 1000, 1200, 1250,
1400, 1600
A
2005
2 - 0 0x0007 Frame size R Encoded The frame size indicates the breaker type.
11: NZM2
12: NZM3
13: NZM4
2006
3 - 0 0x000F Trip type version -
part 1
R Encoded Bit 0: LdSel: with overload protection I
r
= 1
Bit 1: SdSel: with short-time delayed short-circuit
protection I
sd
=1
Bit 2: InstSel: with instantaneous short circuit
release I
i
= 1
Bit 3: GfSel: with ground-fault protection I
g
=1
Bit 4: ARMSel: with maintenance mode = 1
Bit 5: OvrideSel: with instantaneous release func-
tion = 1
Bit 6: not used
Bit 7: MotorSel: with motor-protection function
=1
Bit 8: NeuSenorSel:
0: 3-pole device
1: 4-pole device
Bit 9: ThermalSel: with thermal memory = 1
Bit 12: VoltSel: with voltage meter = 1
Bit 13:
0: PXR20
1: PXR25
2007
Trip type version -
part 2
R Encoded Bit 0: ModbusSel: with integrated Modbus RTU
=1
Bit 1: CAMSel: with CAM RS422 = 1
Bit 2: IOModuleSel: with IO module = 1
Bit 3: RelaySel: with relay module = 1
Bit 4: ZSISel: with zone selectivity = 1
Bit 12: NZM_ACB_Sel:
degree of protection
0: IZMX
1: NZM
Bit 13: IECSel:
0: UL
1: Standard IEC
2008
0 0x0001 Thermal memory
(overload protec-
tion)
R/W Encoded Activates/deactivates the thermal memory of the
overload protection. Recommended for repetitive
testing only.
Among other things, the thermal memory protects
the switch against overheating during repeated
overloads. Reactivate the thermal memory after
testing:
0: switched off
1: switched on