10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.2 EtherCAT
120 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
2009 0 0x0001 ZSI R/W Encoded ZSI, zone-selectivity:
If enabled for releases with ground-fault protec-
tion, ZSI is implemented for both the short-time
delayed short-circuit release and for ground-fault
protection. If enabled for releases without
groundfault protection, ZSI is only implemented
for the short-time delayed short-circuit release.
0: switched off
1: switched on
200A
0 - 1 0x0003 Overload release -
waveform
R/W Encoded Waveform of the overload release
2: I
2
t (default setting)
200B
Settings - release
(I
r
)
R/W Unsigned Settings – overload (I
r
= x * I
n
):
NZM PXR20: R
NZM PXR25: R/W
NZM PXR20:
40: 0.4
45: 0.45
50: 0.5
55: 0.55
60: 0.6
65: 0.65
70: 0.7
75: 0.75
80: 0.8
85: 0.85
90: 0.9
95: 0.95
100: 1.0
The following applies to the NZM PXR25:
General value range: 20 - 1600 (in increments of
1 (1 A))
Caution:
The value range depends on the type:
(e.g. a 250-A switch can be set in the range from
40 % to 100 % of I
n
(value range: 100 - 250)
200C
Settings - over-
load delay time (t
r
)
R/W Unsigned Settings - overload delay time (t
r
= x [s])
NZM PXR20: R
NZM PXR25: R/W
NZM PXR20:
20: 2
40: 4
50: 5
60: 6
70: 7
80: 8
100: 10
120: 12
140: 14
160: 16
180: 18
200: 20
32767: (overload protection deactivated)
s
200D
Load alarm 1 R/W Unsigned Load alarm 1 level (AL1 = n % x I
r
):
50 - 120 (in increments of 1)
%
Index
[Hex]
Bit
field
Mask
field
Setpoint name R/W Format Description or value Unit