10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.2 EtherCAT
PXR Electronic trip unit 01/21 MN012005EN www.eaton.com 129
Table 73: Remote control - EtherCAT
10.2.3.6 Date and time
The release supports the reading and writing of real-time clock information
by the external communication module EtherCAT.
Eight registers, starting with index number 215E, are reserved for this
purpose.
Table 74: Real-time clock - EtherCAT
10.2.3.7 Primary status codes
Table 75: Primary status codes - EtherCAT
Command
group
Definition Bit
Byte 2 Byte 1 Byte 0
Reset Reset the trip 0 0 2
Reset the min./max. values of the L-N voltages1) 0 1 15
Reset the min./max. values of the L-L voltages1) 0 1 14
Reset the peak power requirement1) 0 0 4
Reset all min./max. values 0 1 4
Reset the energy1) 0 0 8
Reset the power-up display 0 0 3
Maintenance
mode
Activate the maintenance mode 1 0 8
Deactivate the maintenance mode 1 0 9
Index [Hex] Definition Data range
215E Month 1 - 12
215F Day 1 - 31
2160 Year 2000 - 2099
2161 Day of the week 1 = Sunday
7 = Saturday
2162 Hour 0 - 23
2163 Minute 0 - 59
2164 Seconds 0 - 59
2165 1/100 of a second 0 - 99
Code Meaning
0x01 open
0x02 closed
0x03 tripped
0x04
Alarm active
0x0D Threshold value active

Table of Contents