10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.2 EtherCAT
130 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
10.2.3.8 Secondary status codes
Table 76: Secondary status codes - EtherCAT
10.2.3.9 Reason codes
Table 77: Reason codes - EtherCAT
Code
Meaning
0x01 not applicable
0x03 Test mode
0x07 has been switched on since last trip / triggered alarm
0x08 Alarm
Code Meaning
0x0000 unknown
0x0001 normal
0x0003 Instantaneous short circuit
0x000E
Auxiliary power supply too low
0x0011 Current imbalance
0x0021 Control via the communication interface
0x0025 Coil monitoring
0x002B Diagnostic warning #2 (configuration read error)
0x003D Overload
0x003E Short-time delay
0x0049 Phase currents are close to the threshold value, load alarm
0x004C
Override
0x004D Setpoint error
0x004E Overtemperature
0x0050
Overload (neutral conductor)
0x0054
Ground fault
0x0071
Calibration
0x0088
Real-time clock
0x0099 Maintenance mode
0x009A Fault in the breaker mechanism
0x07FC Digital bypass
0x07FD Non-volatile memory failure
0x07FE Watchdog fault
0x07FF Motor alarm or motor tripping