10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.3 Profinet
PXR Electronic trip unit 01/21 MN012005EN www.eaton.com 137
10.3.4.2 Real-time data object register
Data that is subject to real-time changes, such as current, voltage and
energy, can be requested via API: 0 and indexes according to table 84.
Real-time data can be obtained either in IEEE floating-point or fixed-point
format. For data displayed in fixed-point format, each result is presented as a
multiplication of the real-time data with a scaling factor.
Energy objects can only be obtained in fixed-point format.
Registers for which the IEEE floating-point value is not specified are only
supported in fixed-point format (FP).
Table 84: Real-time data register - Profinet
1013 Ground-fault protection type is
“source ground”
1029 Ground-fault protection type is
“source ground”
1014
0 1030 0
1015 0 1031 0
1016 0 1032 0
Input
Description or value Input Description or value
Index (Hex) Object
IEEE floating
point
Fixed point
(FP)
Description
(Values in brackets reflect the
American notation.)
Scale factor
(FP)
38 B6 Cause of status:
High byte = primary status
Low byte = secondary status
39
B7 I
L1
(IA) 10
3A B8 I
L2
(IB) 10
3B
B9 IL3 (IC) 10
3C
BA I
G
(IG) 10
3D
BB I
N
( IN) 10
3E
BC U
L1-L2
(VAB) 10
3F BD U
L2-L3
(VBC) 10
40 BE U
L3-L1
(VCA) 10
41 BF U
L1-N
(VAN) 10
42 C0 U
L2-N
(VBN) 10
43 C1 U
L3-N
(VCN) 10
48 C6 Active 3-phase power 1
49 C7 Reactive 3-phase power 1
4A C8 Apparent 3-phase power 1
4B C9 Power factor 100
4C
CA Frequency 10
51 CF Peak active power demand 1

Table of Contents