10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.3 Profinet
PXR Electronic trip unit 01/21 MN012005EN www.eaton.com 155
Table 92: Remote control - Profinet
10.3.4.6 Date and time
The release supports the reading and writing of real-time clock information
by the external communication module Profinet.
Eight registers, starting with index number 15E, are reserved for this
purpose.
Table 93: Real-time clock - Profinet
Command
group
Definition Bit
Byte 2 Byte 1 Byte 0
Reset Reset the trip 0 0 2
Reset the min./max. values of the L-N voltages
1)
0 1 15
Reset the min./max. values of the L-L voltages
1)
0 1 14
Reset the peak power requirement
1)
0 0 4
Reset all min./max. values 0 1 4
Reset the energy
1)
0 0 8
Reset the power-up display 0 0 3
Maintenance
mode
Activate the maintenance mode 1 0 8
Deactivate the maintenance mode 1 0 9
1) PXR25 only!
Index [Hex] Definition Data range
15E Month 1 - 12
15F Day 1 - 31
160 Year 2000 - 2099
161 Day of the week 1 = Sunday
7 = Saturday
162 Hour 0 - 23
163 Minute 0 - 59
164 Seconds 0 - 59
165 1/100 of a second 0 - 99