Appendix A—Parameters
S811+ Soft Starter MN03900001E—November 2012 51
Protections Menu, continued
Advanced I/O Menu
Parameter List—Advanced I/O Setup—All Catalog Numbers
Fault Code Protections Menu Units Minimum Maximum Default Notes
40 3Ø Power Fault—Enable 0 2 0 0 = Disable
1 = Enable
2 = Warning
Low Power Trip Level % 0 100 50
High Power Trip Level % 0 800 125
Pwr Flt Trip Dly seconds 1 60 3
74, 75 Rated Line Freq Hz 50 60 60
Line Freq Fault—Enable 0 2 0 0 = Disable
1 = Enable
2 = Warning
Freq Deviatn Trp % 5 150 50
Freq Trip Delay seconds 1 60 3
59 SCR Short Fault—Enable 0 2 1 0 = Disable
1 = Enable
2 = Warning
58 SCR Cnduct Fault—Enable 0 2 1 0 = Disable
1 = Enable
2 = Warning
38 Temp Sense Fault—Enable 0 2 1 0 = Disable
1 = Enable
2 = Warning
*Alarm-No-Trip 010 0 = Disable
1 = Enable
Advanced I/O
Setup Menu Units Minimum Maximum Default Notes
Access
Level
Input Config Entry 0 = Terminal “1” 0 10 1 0 = No Function
1 = RUN1
2 = Ramp2
3 = JOG
4 = LOCAL
5 = RESET
6 = E-Stop
7 = Alarm-No-Trip
8 = Ext Trip
9 = Ext Warn
10 = Disable OL on Strt (edge only)
11 = Analog
2
Entry 1 = Terminal “2” 0 10 3
Entry 2 = Terminal “3” 0 10 4
Entry 3 = Terminal “4” 0 11 5
Entry 4 = Network Input 1 0 10 0
Entry 5 = Network Input 2 0 10 0
Entry 6 = Network Input 3 0 10 0
Entry 7 = Network Input 4 0 10 0
Run Input Ctrl 0 0 0 0 = Read Only 0
Local Ctrl Only 0 1 0 0 = Disable
1 = Enable
2