EasyManua.ls Logo

Eaton S811+V36 series - Severe Duty-30 Second Ramp And;Or 450% Current; Limit at 50°C-Inline Connection

Eaton S811+V36 series
95 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix C—Ratings, Cooling and Power LossesInline
S811+ Soft Starter MN03900001E—November 2012 59
Severe Duty—30 Second Ramp and/or 450% Current Limit at 50°C—Inline Connection
Notes
1.0SF = 1.0 Service Factor.
1.15SF = 1.15 Service Factor.
Maximum
Current
Three-Phase Motors
Catalog
Number
kW Rating (50 Hz) hp Rating (60 Hz)
230V 380–400V 440V 200V 230V 460V 575–690V
1.0SF 1.0SF 1.0SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
Frame Size N
22 5.510 115 5 7.55 15102015S811+N37N3S
42 1118.5221010151030254030S811+N66N3S
Frame Size R
65 15 30 33 15 15 20 15 50 40 50 50 S811+R10N3S
80 22 40 45 25 20 30 25 60 50 75 60 S811+R13N3S
Frame Size T
115 33 59 63 30 30 40 30 75 75 100 100 S811+T18N3S
150 45 80 90 50 40 50 50 100 100 150 125 S811+T24N3S
192 55 100 110 60 50 75 60 150 125 200 150 S811+T30N3S
Frame Size U
240 75 110 147 75 60 75 75 200 150 200 200 S811+U36N3S
305 90 160 185 100 75 100 100 250 200 300 250 S811+U42N3S
Frame Size V
240 75 110 147 75 60 75 75 200 150 200 200 S811+V36N3S
305 90 160 185 100 75 100 100 250 200 300 250 S811+V42N3S
365 110 185 220 125 100 150 125 300 250 350 300 S811+V50N3S
420 129 220 257 150 125 150 150 350 300 450 350 S811+V65N3S
480 147 257 295 150 150 200 150 400 350 500 450 S811+V72N3S
525 160 280 335 150 150 200 150 450 350 500 450 S811+V85N3S
575 172 303 370 200 150 250 200 500 450 600 500 S811+V10N3S

Table of Contents

Related product manuals