EasyManua.ls Logo

Eaton S811+V36 series - Page 78

Eaton S811+V36 series
95 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix G—Modbus Register Map
68 S811+ Soft Starter MN03900001E—November 2012
Scaled Average Three Phase
Currents in amps—Pole
2 352 R UINT16 Scaled Average pole current in Amps
Scaled Three Phase Currents in
amps—Pole
2 353 R UINT16 L1 RMS pole current in Amps
2 354 R UINT16 L2 RMS pole current in Amps
2 355 R UINT16 L3 RMS pole current in Amps
Scaled Average Three Phase
Currents in deciamps—Pole
2 356 R UINT16 Scaled Average pole current in 0.1 Amps
Scaled Three Phase Currents in
deciamps—Pole
2 357 R UINT16 L1 RMS pole current in 0.1 Amps
2 358 R UINT16 L2 RMS pole current in 0.1 Amps
2 359 R UINT16 L3 RMS pole current in 0.1Amps
Power Factor 2 360 R SINT16 0 to 1.0000 (in 0.0001)
Integer Average Three Phase Real
Power kW
2 361 R UINT16 Average Real Power (kW)
Power Device Pole
Temperature
2 362 R SINT16 L1 pole temp in 0.1°C
2 363 R SINT16 L2 pole temp in 0.1°C
2 364 R SINT16 L3 pole temp in 0.1°C
DC Control Voltage 2 365 R UINT16 DC voltage reported in 0.001V
Device Temperature in Degrees C 2 366 R SINT16 Device temp in 0.1°C
Auto Reset Count 2 367 R UINT16 # of times S811+ has been auto reset
Line Frequency 2 368 R UINT16 Line Frequency (in 0.01Hz)
Line Phase Sequence 1 369 R UINT8 0x01—ABC Phase sequence
0x02—ACB Phase sequence
Fault List
(Fault/Warning codes will be
repeated in the list)
2 370 R UINT16 Latest Fault/Warning code
2 371 R UINT16 2nd Latest Fault/Warning code
2 372 R UINT16 3rd Latest Fault/Warning code
2 373 R UINT16 4th Latest Fault/Warning code
2 374 R UINT16 5th Latest Fault/Warning code
2 375 R UINT16 6th Latest Fault/Warning code
2 376 R UINT16 7th Latest Fault/Warning code
2 377 R UINT16 8th Latest Fault/Warning code
2 378 R UINT16 9th Latest Fault/Warning code
2 379 R UINT16 10th Latest Fault/Warning code
Application Status 2 380 R UINT16 Applications status (present fault)
Motor RUN1input level sense
enable
1 381 R UINT8 0x00—edge sense
0x01—level sense
Modbus Motor Control (3-Wire) 1 500 R/W UINT8 bit
0
1
2
3
4
5
6
7
Description
Run1
Run2
Permissive
Fault Reset
reserved
reserved
reserved
Ramp2 enable
Register Map, continued
Parameter
Data
Length
Modbus
Register
Number Read/Write
Data
Type Description

Table of Contents

Related product manuals