Appendix G—Modbus Register Map
S811+ Soft Starter MN03900001E—November 2012 73
SCR Shorted Fault Enable 1 678 R/W UINT8 0 = Protection disabled
1 = Fault enabled
2 = Warning enabled
Alarm-No-Trip Enable 1 679 R/W UINT8 1 = enable
0 = disable
Motor Control Start Delay
Warning Enable
1 680 R/W UINT8 1 = enable
0 = disable
Motor Control Power on Start
Delay
2 681 R/W UINT16 0.0–600.0 sec (in 0.1 sec)
Motor Control Start Delay 2 682 R/W UINT16 0.0–600.0 sec (in 0.1 sec)
Motor Control Run Command
Change Start Delay
2 683 R/W UINT16 0.0–600.0 sec (in 0.1 sec)
Motor Comm Loss Action 1 684 R/W UINT8 0 = Auto Stop
1 = Auto Run1
2 = Unavailable
3 = Hold Last
4 = Unavailable
5 = Unavailable
6 = Unavailable
7 = All Stop Fault
Transient Motor Control Timeout 2 685 R UINT16 2000 ms
Motor Control Device Command
Missing Timeout
2 686 R UINT16 2000 ms
Network 2 Wire Enable 1 687 R UINT8 0 = Disabled, #500 register active
1 = Enabled. #501 register active
Modbus Device Reset Register 1 800 R/W UINT8 0 = No Reset
1 = Soft Reset
2 = Factory Reset
3 = App parameter Reset
4 = reserved
5 = reserved
6 = Flush Fault History/Queue
7 = Reset Motor Starts
Modbus_User_App_Name 2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
900
901
902
903
904
905
906
907
908
909
910
911
912
913
914
915
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
UINT8
ASCII char#0
ASCII char#1
ASCII char#2
ASCII char#3
ASCII char#4
ASCII char#5
ASCII char#6
ASCII char#7
ASCII char#8
ASCII char#9
ASCII char#10
ASCII char#11
ASCII char#12
ASCII char#13
ASCII char#14
ASCII char#15
Register Map, continued
Parameter
Data
Length
Modbus
Register
Number Read/Write
Data
Type Description