7 Maintenance and service
7.4 Troubleshooting
52 MICRO PANEL XVS400 10.4"/12.1"/15" 10/2011 MN04802012Z-EN www.eaton.com
Tab. 17 Troubleshooting
Touch is deactivated. Start (boot) the device.
Activate touch
(→ Document «MN05010007Z-EN System
Description Windows CE»).
LED «TOUCH ERROR» permanently lit and/or
the icon appears in the taskbar.
Incorrect operation of the operating elements
on the display.
Remove all objects from the area of the display.
Infra-red frame of the infra-red touch is contam-
inated.
Clean the infra-red frame
(→ Chapter 7.2.3, 49).
The threaded pins for mounting the device have
been tightened too much.
Loosen the threaded pins (observe max.
torque, → Chapter 5.4.1, 37).
Device is faulty. Send in your device for repair.
Fault and possible cause Corrective action