7 Maintenance and service
7.4 Troubleshooting
52 MICRO PANEL XVS400 10.4"/12.1"/15" 10/2011 MN04802012Z-EN www.eaton.com
Tab. 17 Troubleshooting
Touch is deactivated. Start (boot) the device.
Activate touch
( Document «MN05010007Z-EN System
Description Windows CE»).
LED «TOUCH ERROR» permanently lit and/or
the icon appears in the taskbar.
Incorrect operation of the operating elements
on the display.
Remove all objects from the area of the display.
Infra-red frame of the infra-red touch is contam-
inated.
Clean the infra-red frame
( Chapter 7.2.3, 49).
The threaded pins for mounting the device have
been tightened too much.
Loosen the threaded pins (observe max.
torque, Chapter 5.4.1, 37).
Device is faulty. Send in your device for repair.
Fault and possible cause Corrective action