EasyManua.ls Logo

Ecom B - Page 20

Ecom B
43 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 20
ecom-B
Another feature of the ecom-B is to deter-
mine the thermal capacity brought to the
boiler. For this the gas meter has to be
observed. By pressing <Enter> a stop-
watch can be started and stopped. The
amount of gas consumed in the meantime
is necessary for calculation and is entered
as follows:
1. Select the position which should be
changed with the keys <store> (left) and
<Print> (right) (corresponding field flashes)
2. Set the value by using the cursers <up /
down>.
After setting and confirmation by pressing
<Enter> the result of the calculation will be
displayed and stored. Calculation can be
repeated if needed. For calculation follow-
ing heating values are taken:
Natural gas (B) = 9,53 kWh/m
3
Town gas (B) = 5,00 kWh/m
3
Coke gas (B) = 4,83 kWh/m
3
Liquid gas (B) = 25,90 kWh/m
3
By using the curser <down> it can be
scrolled to the next measurement Pres-
sure free“. Here is the option for another
pressure measurement.
At the next point of the routine (Curser
<down>) is the option of determination a
temperature difference (W. Temp. warm
W. Temp. cold). For determination of the
two temperatures, the T-Room probe is
used (waterproof version).
Burn. w. blower
W. Temp. kalt
21 °C
Val.: 21 °C
Continue with :
Burn. w. blower
W. Temp. warm
54 °C
Val.: 54 °C
Continue with :
Burn. w. blower
Press. free
4.5 hPa
Val.: 4.5 hPa
Set zero point
CAL.
Burn. w. blower
Gas flow rate
- - . - m3/h
Perfo. - - . - kW
Start :
Burn. w. blower
Gas flow rate
Time: 1 sec
Continue with :
Burn. w. blower
Gas flow rate
4.2 m3/h
Perfo. 40.0 kW
Start :
Burn. w. blower
Gas flow rate
0.100 m3
← →

Related product manuals