12. Technical Data
Parameter Range Measurement principles
O
2
0 ... 21 vol.% electrochemical
CO (without H
2
) 0 ... 2000 ppm electrochemical
CO (with H
2
-option) 0 ...4000 ppm electrochemical
NO (Option) 0 ...5000 ppm electrochemical
CO
2
0 ...CO
2max
calculated
T-G 0 ... 500 °C NiCr-Ni
T-R 0 ... 100 °C semiconductor
Pressure 0 ... +/- 100 hPa DMS-bridge
Efficiency 0 ... 120 % calculated
Losses 0 ... 99,9 % calculated
Lambda 1 ...
calculated
CO-undiluted (reference-O
2
; adjustable) calculated
Dew point of combustion gases calculated
Power Supply 110 - 230 V~ / 50 - 60 Hz;
Battery 6 V / 3,3 Ah
Display: graphic display, backlit
Size (W x H x D) 250 mm x 180 mm x 80 mm
Weight approx. 2,1 kg (complete with sampling system)
Application limits +5 °C to +40 °C;
max. 90 % RH, non-condensing
Subject to technical changes