At the next point of the routine (curser
<down>) there is the option of determina-
tion of a temperature difference (W. Temp.
warm W. Temp. cold). For determination
of the two temperatures the T-Room probe
is used (waterproof version).
Storage of the measurement values (after
getting stable) is done by the key <store>.
By using the curser <down> it can be
scrolled to the next measurement “Temp
free”. Here is the option for another tem-
perature measurement.
After storing the temperatures, the meas-
urement of the combustion gases follows.
By pressing the curser <down> a 1-minute
calibration cycle starts for flashing the sen-
sors with fresh air. During calibration cycle
the probe must not be positioned in the
combustion tube. After calibration cycle,
the combustion measurement at part ca-
pacity can be started. For measurement
the probe must be positioned in the com-
bustion tube. Measurement will be started
by pressing <Enter>. After 90 seconds the
measured values will be automatically
stored for later printout.
Next point of the routine is the combustion
measurement at full capacity by pressing
<Enter>. Also here the values will be
measured after 90 seconds.
The printout (IR printer required) of all re-
sults of the measurement routine could be
done by pressing <Print>.
Burn. w. blower
W. Temp. cold
21 °C
Val.: 21 °C
Continue with :
Burn. w. blower
W. Temp. warm
54 °C
Val.: 54 °C
Continue with :
Burn. w. blower
Difference
33 °C
Continue with :
Burn. w. blower
Temp. free
37 °C
Val.: 37 °C
Continue with :
CO2
12.5 %
O2 4.0 %
CO 30 ppm
Eta 93.0 %
T.Gas 166 °C
T.Air 20 °C
Parti. load
Start :
CO2
12.5 %
O2 4.0 %
CO 30 ppm
Eta 93.0 %
T.Gas 166 °C
T.Air 20 °C
Full load
Start :