CMDN Manual 53
Upon successful compilation, press any key to display the compilation
report. Verify that the digits in the binary code correspond to the
correct configuration parameters, as you entered them in MS-DOS
Editor.
Downloading the Configuration File
For downloading information refer to the Downloading to the
CMDN/SMDN and the CMDN to PC Connections sections.
Upon completion of the download process, the CMDN(-C)/SMDN(-C)
will reboot and operate using the configuration file you just
downloaded.
You can display a complete list of compiler options by typing the
following at the DOS prompt: convert -?
CMDN application for LSS system
; CMDN source file template for LSS CMDN application.
; Definition of commands:
;
; MAX NODES - Must set to 05 for LSS operation.
; ANNUNCIATION - Selects weather a message must be defined locally
; to be annunciated. Selections include GLOBAL
; and LOCAL. Global will allow annunciation of
; messages regardless of weather they are defined
; locally or not.
; EXTERNAL MSG - Must be set to INACTIVE for proper LSS operation.
; FIRE SYSTEM - Must be set to LSS for LSS operation.
; MSG ROUTE - The command allows the filtering of in-coming
; message. Selections include ALL, ALARM,
; SUPERVISORY and TROUBLE.
; NETWORK CLASS - Must be set to class 'B'
; NETWORK BAUD - Must be set to 9600 for LSS operation.
; GEO - Determines display operations for given geographic
; area.
; PRINTER TYPE - Local printer selection.
; PRINTER BAUD - Selects baud rate at which to communicate with
; serial printer.
; SWITCH MASK - Selects which switches are active for both
; switch positions.
; CURRENT ID - Defines the base address of the CMDN.
; ERROR ACTION - Not used for LSS operation set to 0001
;
;:::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::::
MAX NODES 05 ; MUST BE EQUAL TO 05
CURRENT ID 02 ; 01 - 04
FIRE SYSTEM LSS ; FCC A, FCC B, IRC-3, LSS
NETWORK CLASS B ; A, B
NETWORK BAUD 9600 ; 2400, 4800, 9600, 19200
GEO USA ; USA, CANADA, EUROPE