Send a command through the serial interface to close the vent valve before you send a
st
art command. This is known as a delayed start.
If you control the pump with the manufacturer's TIC Turbo and Instrument Controller or
TIC Turbo Controller, the TAV solenoid valve can be operated from the TIC. Refer to the
TIC Instrucon Manuals for more informaon.
4.9.4 Alternave valve connected to the vacuum system
If you use dierent vent valve, make sure that the applicable vent restrictor is installed in
the vacuum system to limit the rate of increase in pressure. Refer to Table: Vent
restrictor orice diameter (with atmospheric pressure at the inlet of the vent valve) for
informaon about the sizes of vent restrictor. If the applicable vent restrictor is not
installed, open the vent valve only when the speed of the pump decreases to 50% of the
full rotaonal speed.
Table 19
Vent restrictor orice diameter (with atmospheric pressure at the inlet of the vent
valve)
Vacuum system volume (litres) Orice diameter (mm)
< 20
£ 1.0
< 10
£ 0.7
< 5
£ 0.5
< 2
£ 0.35
4.10 Cooling
4.10
.
1 Introducon
CAUTION: PUMP COOLING
Risk of damage t
o equipment. Make sure that the pump is suciently cooled to
prevent the damage to the rotor and bearing.
When you use an alternave conguraon (other than the manufacturer's standard
cooling accessories) to cool the pump, make sure that the cooling is not directed or
ducted onto the pump controller.
CAUTION: VENTILATION FOR PUMP
Risk of damage t
o equipment. If the pump is in an enclosure, make sure that
sucient venlaon is available. The ambient temperature around the pump must
not be more than 40 °C.
▪ Natural convecon cooling: For the light pumping dues, with an ambient air
temperature less than 30 °C, natural convecon cooling can be sucient to cool
the pump.
▪ Forced air cooling: The ambient air temperature must be 5 °C to 35 °C when you
use the forced air cooling. make sure that there is sucient supply of cooling air to
the pump.
04/2022 - ©Edwards Limited
Page 60B80000880_G
B80000880_G - Installaon