PD00E0XKNXFI00020100_HANDBOOK_EN.DOCX
PD00E0xKNX KNX PRESENCE DETECTORS RANGE Handbook
Eelectron SpA, Via Monteverdi 6,
I-20025 Legnano (MI), Italia
Tel: +39 0331.500802 Fax:+39 0331.564826
E-mail: info@eelectron.com Web:www.eelectron.com
C.F. e P.IVA 11666760159
Tribunale di Milano 359157-8760-07
CCIAA Milano 148549
35/46
valve valve
cool heat
Additional valve 6 ways
The additional valve also manages commands for 6-
way valves in which the control value from 0% to
100% defines both the percentage of valve opening
and the passage of hot or cold fluid.
KNX PARAMETER
SETTINGS
Percentage 100% cool
0% ÷ 30%
Value to be sent to bring the cold valve to 100% open
position [point A on the diagram]
Percentage 0% cool
23% ÷ 53%
Value to be sent to bring the cold valve in closed
position (0% open) [point B of the diagram]
Percentage 0% heat
47% ÷ 77%
Value to be sent to bring the hot valve to the closed
position (0% open) [point C of the diagram]
Percentage 100% heat
70% ÷ 100%
Value to be sent to bring the hot valve to 100% open
position [point D on the diagram]
Value to send for valve
fully closed
36% ÷ 66%
Value to be sent to bring both the cold and hot valves to
the fully closed position. [area of the diagram between B
and C]
For the additional valve, in 6-way mode, it is
possible to define different control differentials
around the setpoint value as shown below:
This makes it possible to adjust the opening and
closing of the additional valve independently of the
speed control (for example, once the setpoint has
been exceeded, a maintenance action can be taken
keeping the valve open again without activating the
speeds)
KNX PARAMETER
SETTINGS
Regulation differential
valve 0%
0°C ÷ 5 °C
Defines the width of the F-G bands for cooling and H-I
for heating
Regulation differential
valve 100%
0°C ÷ 5 °C
Defines the width of the E-F bands for cooling and I-L
for heating
Force fan coil speed
In fan coil operation (in 1-bit or 1-byte mode), you
can force the use of just one speed and bypass the
automatic speed selection. This mode is useful, for
example, in small rooms such as hotel rooms, for
example or in any case where the fan speed may
bring noise. To activate forcing, you must act on the
1-bit object that selects AUTO / MAN and then on
the object that activates the desired speed (3x1 1-
bit object or 1 object at 1-byte in% mode)
Ventilation mode
When using fan coil, you can also activate "fan" or
"ventilation" mode. In this mode, the fan coil will
never turn off the fan even when, after reaching the
100%
0%
100%
A
B
C
D
Value to send
Setpoint heating
E
Setpoint cooling
F
G
H
I
L
Cool valve open (100%)
Cool valve close (0%)
Heat valve close (0%)
Heat valve open (100%)