5.5 Demands
5.5.1 Present Demands
Register
Property
Description
Format
Scale
Unit
3000
RO
Ia
Float
x1
A
3002
RO
Ib
Float
3004
RO
Ic
Float
3006
RO
kW Total
Float
x1
W
3008
RO
kvar Total
Float
x1
var
3010
RO
kVA Total
Float
x1
VA
Table 5-12 Present Demand Measurements
Notes:
1) When the Wiring Mode is 1P2W L-N or 1P2W L-L, the Ib/Ic Present Demand have no meaning, and
their registers are reserved.
2) When the Wiring Mode is 1P3W, the Ic Present Demand has no meaning, and its register is reserved.
5.5.2 Predicted Demands
Register
Property
Description
Format
Scale
Unit
3200
RO
Ia
Float
x1
A
3202
RO
Ib
Float
3204
RO
Ic
Float
3206
RO
kW Total
Float
x1
W
3208
RO
kvar Total
Float
x1
var
3210
RO
kVA Total
Float
x1
VA
Table 5-13 Predicted Demand Measurements
Notes:
1) When the Wiring Mode is 1P2W L-N or 1P2W L-L, the Ib/Ic Predicted Demands have no meaning,
and their registers are reserved.
2) When the Wiring Mode is 1P3W, the Ic Predicted Demand has no meaning, and its register is
reserved.
5.5.3 Maximum Demand Log of This Month (Since Last Reset)
Register
Property
Description
Format
Scale
Unit
3400~3405
RO
Ia
See
Section 5.5.5
Demand Data
Structure
x1
A
3406~3411
RO
Ib
3412~3417
RO
Ic
3418~3423
RO
kW Total
W
3424~3429
RO
kvar Total
var
3430~3435
RO
kVA Total
VA
Table 5-14 Maximum Demand Log of This Month (Since Last Reset)
Notes:
1) When the Wiring Mode is 1P2W L-N or 1P2W L-L, the Ib/Ic Maximum Demand of This Month (Since
Last Reset) registers have no meaning, and their registers are reserved.
2) When the Wiring Mode is 1P3W, the Ic Maximum Demand of This Month (Since Last Reset) and its
register is reserved.
5.5.4 Maximum Demand Log of Last Month (Before Last Reset)
Register
Property
Description
Format
Scale
Unit
3600~3605
RO
Ia
See
Section 5.5.5
Demand Data
Structure
x1
A
3606~3611
RO
Ib
3612~3617
RO
Ic
3618~3623
RO
kW Total
W
3624~3629
RO
kvar Total
var
3630~3635
RO
kVA Total
VA
Table 5-15 Maximum Demand Log of Last Month (Before Last Reset)
Notes:
1) When the Wiring Mode is 1P2W L-N or 1P2W L-L, the Ib/Ic Maximum Demand of Last Month
(Before Last Reset) registers have no meaning, and their registers are reserved.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EET PMC-33M-A and is the answer not in the manual?

EET PMC-33M-A Specifications

General IconGeneral
BrandEET
ModelPMC-33M-A
CategoryMeasuring Instruments
LanguageEnglish