Page #53 background imageLoading...
Page #53 background image
CET Electric Technology
53
This Month (Since Last Reset)
1
9604
WO
Clear All Demand Registers
2
9605
WO
Clear Max./Min. Logs of This Month
(Since Last Reset)
3
9606
WO
Clear All Max./Min. Log
4
9607
WO
Clear Device Operating Time
9608
WO
Clear All Data
5
9609
WO
Clear SOE Log
9610
WO
Clear DI1 Pulse Counter
9611
WO
Clear DI2 Pulse Counter
9612
WO
Clear DI3 Pulse Counter
9613
WO
Clear DI4 Pulse Counter
9614~9617
WO
Reserved
9618
WO
Clear All Pulse Counters
Table 5-33 Clear Control
Notes:
1) Writing 0xFF00 to the Clear Maximum Demand of This Month register to clear Maximum Demand
Log of This Month (Since Last Reset) when the Self-Read Time register is set for automatic Self-
Read operation. The Maximum Demand of Last Month will not be cleared. If the Self-Read Time
register is set for manual operation with a register value of 0xFFFF, the Maximum Demand of This
Month (Since Last Reset) will be transferred to the Maximum Demand of Last Month (Before Last
Reset) and then cleared.
2) Writing 0xFF00 to the Clear All Demand register to clear all Demand registers and logs, including
Real-time Present Demand, Maximum Demand Log of This Month (Since Last Reset) and Last
Month (Before Last Reset).
3) Writing 0xFF00 to the Clear Max./Min. Log of This Month register to clear the Max./Min. log of
This Month (Since Last Reset) when the Self-Read Time register is set for automatic Self-Read
operation. The Max./Min. log of Last Month will not be cleared. If the Self-Read Time register is set
for manual operation with a register value of 0xFFFF, the Max./Min. log of This Month (Since Last
Reset) will be transferred to the Max./Min. log of Last Month (Before Last Reset) and then cleared.
4) Writing 0xFF00 to the Clear All Max./Min. Log register to clear both the Max./Min Log of This
Month (Since Last Reset) and the Max./Min. Log of Last Month (Before Last Reset).
5) Writing 0xFF00 to the Clear All Data register to perform the Clear operation for the actions specified
in registers # 9601 to # 9607, registers # 9609 to # 9613 and register # 9618.
5.12 Meter Information
Register
Property
Description
Format
Note
60200~60219
9800~9819
RO
Meter model
1
UINT16
See Note 1)
60220
9820
RO
Firmware Version
UINT16
e.g. 10000 shows the
version is V1.00.00
60221
9821
RO
Protocol Version
UINT16
e.g. 10 shows the
version is V1.0
60222
9822
RO
Firmware Update
Date: Year-2000
UINT16
e.g. 140110 means
January 10, 2014
60223
9823
RO
Firmware Update
Date: Month
UINT16
60224
9824
RO
Firmware Update
Date: Day
UINT16
60225
9825
RO
Serial Number
UINT32
e.g. 1701030100 means
the 100
th
PMC-33M-A
that was manufactured
on January 3
rd
, 2017
60227
9827
RO
Reserved
UINT16
60228
9828
RO
Reserved
UINT16
60229
9829
RO
Feature Code
UINT16
Bit 6 to Bit 0: Reserved
Bit 7 (DIDO):
0=4xDI + 2 x SS Pulse
Output
1=None
Bit 8 to Bit 16: Reserved
Table 5-34 Meter Information

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EET PMC-33M-A and is the answer not in the manual?

EET PMC-33M-A Specifications

General IconGeneral
BrandEET
ModelPMC-33M-A
CategoryMeasuring Instruments
LanguageEnglish