CET Electric Technology
50
2) There are two ways to calculate THD:
THDf (based on Fundamental):
%100THD
1
2
2
I
I
n
n
where I
n
represents the RMS value for the n
th
harmonic and I
1
represents the RMS value of the
Fundamental harmonic.
THDr (based on RMS):
%100THD
1
2
2
2
n
n
n
n
I
I
where I
n
represents the RMS value for the n
th
harmonic.
3) The Self-Read Time applies to both the Maximum Demand Log as well as the Max./Min. Log and
supports the following three options:
A zero value means that the Self-Read will take place at 00:00 of the first day of each month.
A non-zero value means that the Self-Read will take place at a specific time and day based on
the formula: Self-Read Time = (Day x 100 + Hour) where 0 Hour 23 and 1 Day 28. For
example, the value 1512 means that the Self-Read will take place at 12:00pm on the 15th day
of each month.
A 0xFFFF value means the automatic self-read operation is disabled and the log will be
transferred manually.
5.8.2 I/O Setup (Optional)
Register
Property
Description
Format
Range, Default*
6200
RW
DI1 Function
UINT16
0 =Digital Input*
1=Pulse Counting
6201
RW
DI2 Function
UINT16
6202
RW
DI3 Function
UINT16
6203
RW
DI4 Function
UINT16
6204~6207
Reserved
6208
RW
DI1 Debounce
UINT16
1 to 9999 ms,
20*
6209
RW
DI2 Debounce
UINT16
6210
RW
DI3 Debounce
UINT16
6211
RW
DI4 Debounce
UINT16
6212~6215
Reserved
6216
RW
DI1 Pulse Weight
UINT32
1* to 1,000,000
6218
RW
DI2 Pulse Weight
UINT32
6220
RW
DI3 Pulse Weight
UINT32
6222
RW
DI4 Pulse Weight
UINT32
6224~6235
RW
Reserved
UINT16
-
6236
RW
DO1 Pulse Width
UINT16
0 to 6000 (x0.1s), 10*
(0 = Latch Mode)
6237
RW
DO2 Pulse Width
UINT16
Table 5-26 I/O Setup Parameters
5.8.3 Communication Setup Parameters
Register
Property
Description
Format
Range, Default*
6400
RW
Port 1 Protocol
UINT16
0=Modbus RTU*
6401
RW
Port 1 Unit ID
UINT16
1 to 247, 100*
6402
RW
Port 1 Baud Rate
1
UINT16
0=1200, 1=2400, 2=4800,
3=9600*, 4=19200, 5=38400
6403
RW
Port 1 Comm. Config.
UINT16
0=8N2, 1=8O1,2=8E1*
3=8N1, 4=8O2, 5=8E2
Table 5-27 Communication Setup
Notes:
1) If the Baud Rate is set to an invalid value, it will default to 9600bps automatically.