E F A P O W E R EV- H C - I N S T A L L A T I O N A N D U S E R M A N U A L
25 | 28
8 MAINTENANCE MANUAL
ALL SERVICING MUST BE PERFORMED ONLY BY QUALIFIED PERSONNEL. DO NOT ATTEMPT TO SERVICE THE
EFAPOWER EV-HC STATION YOURSELF.
BY OPENING THE EFAPOWER EV-HC STATION’S COVERS YOU RUN RISK OF EXPOSURE TO DANGEROUS
VOLTAGES!
IN CASE OF ANY KIND OF DOUBT REGARDING THIS, PLEASE CONTACT:
EFACEC WILL ASSUME NEITHER RESPONSIBILITY NOR LIABILITY DUE TO INCORRECT OPERATION OR
MANIPULATION OF THE EFAPOWER EV-HC STATION.
After discovering any malfunction, please check the troubleshooting section 8.2 of this manual, and act
accordingly to reach a resolution. If none of the actions solved the malfunction, please contact the local technical
support.
Equipment identification and detail description of the malfunction will be required for the remote support.
Please note that Efacec does not refund travel or shipping expenses.
The company does not hold any responsibility for any damages caused after the warranty period, but will gladly
provide its customers with any technical consulting.
8.1 PREVENTIVE MAINTENANCE
This equipment must be kept in perfect condition to guarantee a safe and efficient battery charge. Make sure
dust and moisture are kept out of the EV-HC.
It is also important to ensure that a complete test is carried out by a qualified technician on a yearly or bi-yearly
basis.
We advise to carry out the following verifications:
Table 7 - EFAPOWER EV-HC Preventive Maintenance
Operation
Periodicity
Estimated time(min)
Tools
Visual checking of the installation
Including AC input cables: Check the
tightening torque of the cable
connections.
Each 6 months
10
Standard Tools
Torque wrench
Check value of protective earth
Each 6 months
5
Multimeter
Standard Tools
Output cables: check if the connectors,
cables and its connections are in perfect
condition.
Each 6 months
5
Standard Tools
Torque wrench
Test RCD by pressing the RCD test button
Each 6 months
Standard Tools