Even though, non-conductive dust does not influence the system’s operation, it may however, with excessive
accumulation, not allow proper cooling, therefore limiting the equipment’s thermal capabilities. Consequently,
dust accumulation must be avoided in order to guarantee a better thermal performance.
Conductive dust and acid vapors must be kept away from the Quick Charger.
On locations with harsh weather conditions (high temperatures, heavy dust, snow and/or very low
temperatures) it’s recommended to provide additional protection, either inside a building or a shelter, or
providing a protection roof for the Unit. See example in Figure 6.
Figure 6 - EFAPOWER EV-QC45 with shelter
5.1.2 SITE VERIFICATION AND INSPECTION
Check if the installation of the Quick Charger is not planned to be made in a commercial garage (repair
facility) or closer than 508mm (20 feet) of an outdoor motor fuel dispensing device;
Check if the access passages to the Quick Charger Station layout site are not blocked in order to allow its
transportation;
Check if Quick Charger Station layout site is compliant with the specified clearance around the cabinet.