EasyManua.ls Logo

Electro-Voice Precision P1200RL - CAN-BUS Specifications; Data Rates, Bus Lengths, and Cables

Electro-Voice Precision P1200RL
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14
The CAN-bus allows using different data rates, with the data
rate being indirectly proportional to the bus length. Small net
works allow baud rates up to 500kbit/s.
For sizable dimensioned networks reducing the baud rate
(minimum 10kbit/s) is necessary. The integration of
repeaters is generally recommended when the bus-length
exceeds 1,000m
.
Baud Rate
Bus Length
500 kbit/s
100 m
250 kbit/s
250 m
125 kbit/s
500 m
62.5 kbit/s
1000 m
20 kbit/s
2500 m
10 kbit/s
5000 m
CAN-BUS CABLE SPECIFICATIONS
According to the ISO 11898-2 standard, CAN-bus data transfer cabling has to be carried out using
Twisted-Pair cables with or without shielding providing a characteristic impedance of 120
. Both ends of
a CAN-bus need to be terminated with 120
termination-plugs.
The maximum bus-length depends on the actual data transfer rate, the kind of data transfer cable being
used, as well as the total number of participants on the bus. The following table shows the most essential
coherencies for CAN-networks consisting of up 64 participants
:
Bus Length
Cable for data Transmission
Termination
Max.
Data Transfer Rate
Resistance per
Unit Length
Cable Diameter
0 ... 40 m
< 70 m
/m
0.25 ... 0.34 mm²
AWG23, AWG22
124
1000 kbit/s bei 40 m
40 ... 300 m
< 60 m
/m
0.34 ... 0.6 mm²
AWG22, AWG20
127
500 kbit/s bei 100 m
300 ... 600 m
< 40 m
/m
0.5 ... 0.6 mm²
AWG20
150
... 300
*
100 kbit/s bei 500 m
600 ... 1000 m
< 26 m
/m
0.75 ... 0.8 mm²
AWG18
150
... 300
*
62.5 kbit/s bei 1000 m
*
With longer cables and many participants on the CAN-bus, termination resistors with higher impedance than the
speci ed 120
are recommended to reduce the ohmic load of the interface drivers and therefore the voltage drop
between the two cable ends
.
The following table is meant for  rst assessment of necessary cable diameters for different bus lengths
and bus-participant numbers
:
Bus Length
Number of Appliances on the CAN-Bus
32
64
100
100 m
0.25 mm² bzw. AWG24
0.34 mm² bzw. AWG22
0.34 mm² bzw. AWG22
250 m
0.34 mm² bzw. AWG22
0.5 mm² bzw. AWG20
0.5 mm² bzw. AWG20
500 m
0.75 mm² bzw. AWG18
0.75 mm² bzw. AWG18
1.0 mm² bzw. AWG17
Additionally, the length of branch lines – for participants that are not directly connected to the CAN-bus
is also of importance. For data transfer rates of up to 125kbit/s, the maximum length of a single stub
cable should not exceed 2m. For higher bit rates a maximum length of only 0.3m is still permissible. The
entire length of all branch lines should not exceed 30 m.
General Note:
As long as only short distances (up to 10m) are concerned, common RJ-45 patch cables with
100
characteristic impedance (AWG 24 / AWG 26) can be used for the cabling inside of a rack-
shelf system. The previously outlined guidelines for network cabling are mandatory as far as the
rack-shelve interconnection or  xed installations are involved
.
CAN-BUS

Other manuals for Electro-Voice Precision P1200RL

Related product manuals