68
Page
Locate terminal on wall and predrill mounting holes where
required.
Cut flue exhaust tube (hot tube) to length (Flue must
extend a minimum of 50mm past the exit face of wall.) It
is recommended that the tubes are cut slightly longer and
pushed back into wall upon fixing of wall terminal. Allow
flue movement between terminal and last flue hanging
clip.
Cut Air intake as per flue exhaust.
Ensure ends are burr free and round, test fit flue will slide
inside both the hot exhaust connection and air intake
connection.
Feed hot exhaust flue
into connection, ensure
inserted 50mm. Fit retaining
screw from below.
Feed air intake flue
into connection, ensure
inserted 50mm. Fit retaining
screw from below.
Insulation must start as close to the gas space heater as
possible
(Only exhaust flue is to be insulated)
Insulation to be fully closed
and sealed along length.
Fit flue exhaust insulation
Insulated with 25mm foil
faces glasswool pipe
insulation, as supplied by
Glen Dimplex Australia.
Bends were practical
should be insulated, by
cutting the insulation into
segments and taping
together.
Joins can be taped
together using aluminum
foil self adhesive tape.