17
8.6 DIP-SWITCH 6 - Self-holding enable (start/stop floats)
Self-holding disabled (start/stop floats)
Self-holding enabled (start/stop floats)
DIP-SWITCH 6 is used to activate the self-holding function for start/stop floats for wastewater
emptying.
For this setting, the stop float must be connected to the C-MAX input and the start float to G/P1
and G/P2.
In the OFF position, the operation with float self-holding is disabled.
In the ON position, the operation with float self-holding is enabled.
NB: Do not activate on pressurization plants. Activate on emptying mode only if C-MIN-MAX
input is used with floats or level probes.
8.7 DIP-SWITCH 7 - Delayed board activation enable on mains power return
Deactivation of board delay on mains power return
Activation of board delay on mains power return
DIP-SWITCH 7 is used for delayed board activation on mains power return.
In the OFF position, the board will be activated immediately on power return.
In the ON position, the board will be activated 30 seconds after power return.
N.B. after a power supply failure, the board is reactivated maintaining the previous AUT -0 MAN
status.