EasyManua.ls Logo

Elentek SMART PRO - RS485 Modbus Communication Addresses

Elentek SMART PRO
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
32
15. RS485 MODBUS ADDRESSES
0x100
Board data
0x101
Board serial number
0x102
Voltage of board 1 in V
0x103
Voltage of board 2 in V
0x104
Current of pump 1 in A/10
0x105
Current of pump 2 in A/10
0x106
Current of pump 3 in A/10
0x107
Current of pump 4 in A/10
0x108
Cos-fi of pump 1 in/100
0x109
Cos-fi of pump 2 in/100
0x10A
Cos-fi of pump 3 in/100
0x10B
Cos-fi of pump 4 in/100
0x10C
Dip-Switch status
0x10D
Input status
0x10E
Output status
0x10F
Alarm 2 status
0x110
Alarm 1 status
0x111
Free
0x112
Free
0x113
Free
0x114
Free
0x115
Free
0x116
Alarm 2 reset
0x117
Alarm 1 reset
0x118
MANUAL control logical status
0x119
AUTOMATIC control logical status
0x11A
P1 hours of operation
0x11B
P2 hours of operation
0x11C
P3 hours of operation
0x11D
P4 hours of operation
0x11E
Program to be followed
0x11F
Type of Alarm Timer
0x120
Language
0x121
Display brightness on standby
0x122
ELENTEK name displayed on panel
0x123
Panel name enable
0x124
Klixon self-reset
0x125
Max. settable current in A/10
0x126
Alarm inhibition time at start in s/10

Table of Contents