17. TROUBLESHOOTING
PROBLEM
CHECKS/SOLUTIONS
THE POWER ON LED
FLASHES
Check that all phases are available at the panel input.
Check and modify the phase sequence at the input of the door lock
disconnect switch.
THE PANEL IS POWERED
UP BUT THE MOTOR
DOES NOT START
Check that the green led on the automatic mode key is lit;
otherwise press the key.
Check input status and settings.
THE PANEL IS SET TO
AUTOMATIC MODE BUT
THE MOTOR DOES NOT
START.
Check input status and settings.
On the single phase model, check that the 230V~ voltage is present
on the motor output terminals “L/S” and “N/R”; on the three-
phase model check that the 400V~ voltage is present on terminals
“L/S” and “N/R” and that the contactor winding is powered.
ON PUMP START-UP,
THE THERMAL SWITCH
TRIPS.
Check the maximum current setting in the settings.
Check the motor current with a current clamp.
Check the motor status
THE THERMAL SWITCH
DOES NOT TRIP.
Check the maximum current setting in the settings.
THE PANEL IS IN MOTOR
OVERTEMPERATURE
ALARM STATUS
Check that the over-temperature control is disabled if the motor/s
is/are not fitted with a thermal switch.
Check the motor status
NO LED LIGHTS UP ON
THE CONTROL PANEL.
Check that the FLAT connector is inserted correctly.
Ensure that the door lock is set to ON.
On the panel input, check that the voltages 230V~ or 400V~ are
present between the SUPPLY mains input terminals.
Check that the fuses are efficient.