13 KEYS AND INDICATORS FOR THE OPERATOR
KEY FUNCTION
ACK
( )
This key must be pressed to acknowledge the events (alarms, faults,
maintenance) detected by the control panel.
RESET
This key starts the “Global Reset” procedure.
Whenever the user presses this key, an event is stored in the event log and, if
the passwords are enabled, the level 2 password is required.
SILENCE /
REARM SIREN
This key stops and restarts the siren output and the alarm outputs of the actuators after
the occurrence of an alarm. Whenever the user presses this key, an event is stored in the
event log and, if the passwords are enabled, the level 2 password is required.
SKIP DELAY
This key makes the siren output activation delay expire immediately when the
control panel is in alarm condition of a zone/group alarm in timer mode and the
timer is running.
By pressing this key the control panel will ignore the delay and will
activate the siren output immediately.
INCREASE DELAY
In order for this key to have an effect, the timer of a zone/group alarm in time
mode must be running. In this situation, when this key is pressed the current
value of the running timer is increased by 1 minute. The maximum overall time
(initial delay + increments due to the key) is 10 minutes. Whenever the user
presses this key, an event is stored in the event log and, if the passwords are
enabled, the level 2 password is required.
MASTER ALARM
When the control panel is in monitoring phase, this key triggers the general alarm
condition. Whenever the user presses this key, an event is stored in the event
log and, if the passwords are enabled, the level 2 password is required.
INCLUDE/EXCLUDE
When the control panel is in monitoring phase, this key allows the user to
include/exclude circuits, zones, groups, points or any other equipment connected
to the control panel. When the user presses this key, the level 2 password is
required (if passwords are enabled).